HIGH LEVEL INTERFACE
UL S3217
P/N 06-158
33
FM 3020297
Rev 5, 02/2015
If wiring is reconnected or communication to HLI is restored, the following event will be displayed:
V E S D A
R E T U R N :
V Z 0 0 1
C U S T O M M S G
P A N E L
0 0 1
0 8 : 4 5 : 2 2 A
1 1 / 1 5 / 2 0 0 5
E V E N T
0 0 1 3
O F
0 0 1 3
Exhibit 40: CyberCat/Cheetah Xi– Trouble Restored
Line 1 VESDA Detector communicating with panel has been restored.
Line 2 Custom Message of panel HLI is connected to.
Line 3 Time and date stamp for this event
Line 4 Event number and total events on panel
If the wiring from the HLI to the VESDANet is open, the following event description will be seen:
N E T W O R K
F A U L T :
V Z 0 0 1
C U S T O M M E S S A G E
V Z 0 0 1
0 9 : 2 5 : 2 2 A
1 1 / 1 5 / 2 0 0 5
E V E N T
0 0 1 5
O F
0 0 1 5
Exhibit 41: CyberCat/Cheetah Xi– Trouble Restore
Line 1 VESDA Detector no longer communicating with panel.
Line 2 Custom Message of panel HLI is connected to.
Line 3 Time and date stamp for this event
Line 4 Event number and total events on panel
Once the trouble with the RS485 wiring between the HLI and the VESDA has been restored, the screen will
display:
N E T W O R K
F
C L R :
V Z 0 0 1
C U S T O M M E S S A G E
V Z 0 0 1
0 9 : 2 6 : 3 8 A
1 1 / 1 5 / 2 0 0 5
E V E N T
0 0 1 6
O F
0 0 1 6
Exhibit 42: CyberCat/Cheetah Xi– Trouble Restore
Line 1 VESDA Detector communicating with panel has been restored.
Line 2 Custom Message of panel HLI is connected to.
Line 3 Time and date stamp for this event
Line 4 Event number and total events on panel