APPENDIX 2 - CYBERCAT / CHEETAH Xi EVENT MESSAGES
ACTION LEVEL: VZ nnn
The VESDA detector programmed
as Zone nnn has reached the Action
Level (Level 2).
Locate the detector by using the
custom message on the 2nd line
and the address and obscuration of
the device by pressing F1 on the
display. Determine cause for
elevated obscuration.
ACTION CLEAR: VZ nnn
The VESDA detector programmed
as Zone nnn has dropped below the
previously reached Action Level.
None
ALERT LEVEL: VZ nnn
The VESDA detector programmed
as Zone nnn has reached the Alert
Level (Level 1).
Locate the detector by using the
custom message on the 2nd line
and the address and obscuration of
the device by pressing F1 on the
display. Determine cause for
elevated obscuration.
ALERT CLEAR: VZ nnn
The VESDA detector programmed
as Zone nnn has dropped below the
previously reached Alert Level.
None
FIRE-1 LEVEL: VZ nnn
The VESDA detector programmed
as Zone nnn has reached the Fire-1
Level (Level 3).
Locate the detector by using the
custom message on the 2nd line
and the address and obscuration of
the device by pressing F1 on the
display. Determine cause for
elevated obscuration.
FIRE-2 LEVEL: VZ nnn
The VESDA detector programmed
as Zone nnn has reached the Fire-2
Level (Level 4).
Locate the detector by using the
custom message on the 2nd line
and the address and obscuration of
the device by pressing F1 on the
display. Determine cause for
elevated obscuration.
ISOLATE FAULT: VZ nnn
The VESDA detector programmed
as Zone nnn is isolated/disabled.
Locate VESDA Zone nnn and de-
isolate or determine reason it is
currently isolated.
ISOLATE F CLR: VZ nnn
The VESDA detector, Zone nnn,
which previously reported ISOLATE
FAULT, has cleared.
This is an expected event if the
detector is de-isolated. Note events
if desired.
MAJOR FAULT: VZ nnn
The VESDA detector programmed
as Zone nnn has a major fault.
Locate VESDA Zone nnn and
connect with software or
programmer to diagnose fault.
MAJOR FLT CLR: VZ nnn
The VESDA detector, Zone nnn,
which previously reported MAJOR
FAULT, has cleared.
This is an expected event if the
VESDA fault is cleared. Note
events if desired.
MINOR FAULT: VZ nnn
The VESDA detector programmed
as Zone nnn has a MINOR FAULT.
Locate VESDA Zone nnn and
connect with software or
programmer to diagnose fault.