CiTRANS R820 Edge Router Hardware Description
2.7
Technical Parameters
Table 2-6
PDP250B Technical Parameters
Item
Performance Specification
Input
Input voltage range (V)
-38 to -58
Maximum input current
(A)
50 per branch
Output
Output voltage range (V)
-37 to -59
Output branch
6 output branches
Output current (A)
32 per branch
Alarm function
Alarm signal processing
function
Receive an alarm signal reported by the equipment,
generate audio alarms for the signal, drive the cabinet
indicator, and output the alarm signal to the upper-
level equipment (such as the head of row cabinet).
Lightning protection
module alarm reporting
function
When the lightning protection module fails, output the
lightning protection module failure alarm to the
OTNM2000.
Electromag-
netic
compatibility
(EMC)
Electromag-
netic
interference
(EMI)
Radiated emission (RE)
Comply with the EN55022 Class B standard.
Conducted emission
(CE)
Comply with the EN55022 Class B standard.
Electromag-
netic
susceptibility
(EMS)
Electrostatic discharge
(ESD)
Comply with the IEC61000-4-2 standard.
Radiated susceptibility
(RS)
Comply with the IEC61000-4-3 standard.
Electrical fast transient
(EFT)
Comply with the IEC61000-4-4 standard.
Surge
Comply with the IEC61000-4-5 standard.
Conducted susceptibility
(CS)
Comply with the IEC61000-4-6 standard.
Voltage dip (DIP)
Comply with the IEC61000-4-29 standard.
Safety regulation
Comply with the IEC60950 standard.
DC lightning protection
Differential mode
protection
An 8/20us 2kA test surge current is imposed in the
positive and negative directions between the external
power input terminals -48 V and 0 V. The PDP can
work normally after the surge current is imposed.
2-10
Version: A