4. Press the Enter key to open the menu FIELDBUS.
PROFIBUS-DP
STATION ADDRESS
5. Press the Enter key to select the command
STATION ADDRESS.
STATION ADDRESS
000?
6. Use the cursor keys to set the desired PROFIBUS
ADDRESS. Then press the Enter key. A system
reset is required before you can transfer the new
PROFIBUS address. The following question there-
fore appears.
UPDATE NEW ADDR.
SYSTEM RESET ?
7. You can now abort with ESC or trigger a system
reset with ENTER and thereby confirm the new ad-
dress.
After a system reset, the SPC200 is reset to the status
it was in when switched on. A program reset and a
hardware recognition are carried out here and the axis
interface string is initialized again. Depending on the
system configuration used, this procedure may take a
certain amount of time.
4. Commissioning
SPC200-COM-PDP 9904NH
4-13