Terminating resistor (cable termination)
Bus segments must be concluded at both ends with a
terminating resistor. This also applies if the module or
communication processor is at the end of the bus
cable.
Recommendation: Use plugs with an integrated termi-
nating resistor if you are connecting the SPC200 at the
end of a bus segment. If necessary, switch in the termi-
nating resistor.
The diagram below shows the circuitry of the terminat-
ing resistor combination of cable A as per EN 50 170.
Pin 6:
Power supply
Pin 3:
RxD/TxD-P
Pin 8:
RxD/TxD-N
Pin
5: DGND
Fig. 3/3: Cable termination as per EN 50 170 (cable A)
390
220
390
Pin 6
Pin 3
Pin 8
Pin 5
3. Installation
3-8
SPC200-COM-PDP 9904NH