SOPA-...
30
Festo – SOPA-... – 2017-09b English
Setting supply pressure monitoring for Out C:
Note
The binary signal Out C is pre-configured for monitoring the supply pressure with the
control module SOPA-C. When using the control module SOPA-C, we recommend you
keep these factory settings.
Changing the switching points for the binary signal Out C is only expedient if you are
using a precision controller to operate the sensor modules instead of the control
module.
1. Press the Edit button.
The EDIT mode is active and [Out A] flashes or, if there is an active security lock, [Lock] flashes.
2. If there is an active security lock, it must be released:
Press the A/B pushbuttons until the chosen security code is set.
Press the Edit button.
è
The EDIT mode is active and [Out A] flashes.
3. Press the A/B pushbuttons until [Out C] flashes.
4. Press the Edit button to confirm the selection.
è
[SP min] flashes.
5. Set the switching point by using the A/B pushbutton.
6. Press the Edit button to confirm the value.
è
[SP max] flashes.
7. Set the value for the switching point by using the A/B pushbuttons.
8. Press the Edit button to confirm the value.
è
[NO] or [NC] flashes.
9. Select the switching element function using the A/B pushbuttons.
10.Press the Edit button to confirm the value.
è
SOPA switches to RUN mode.
Conduct a test run and vary the supply pressure to check whether the SOPA switches as desired.
Recommendation: Teach-in the value for Out A again after changing the switching points for Out C.