ERROR CODES, ALARMS/INFO
When the ALARM LED is lit, notifications in progress
can be seen on the display (e.g.
Er
07
, or multiple
notifications e.g.
Er
07
16
):
-
when the board is not in the programming menus,
press
++
and
--
at the same time.
32
Motion timeout
The movement is in timeout.
Check the manual release of the motors.
Check the presence of mechanical stops.
If limit switches are installed, make sure
that they activate correctly.
If the problem persists, replace the board
or motor.
35
BUS 2easy device
fault / conflict
Check the addresses of the devices.
36
BUS 2easy short cir-
cuit / overload
Check the connections of the BUS 2easy
devices that are connected and reg-
istered.
38
Programming pa-
rameters changed
Modified programming, NOT consistent
with the
SETUP
.
Restore the previous settings or carry out
the
SETUP
procedure.
39
SETUP
incorrect or
missing
Perform
SETUP
.
41
(
i)
Date/time miss-
ing
TIMER
date/time missing.
Replace the buffer battery BAT1 -
CR2032, then reset the time and date
on the board (from
Simply Connect
).
42
(
i)
Partial open
Automation is in partial open mode.
44
(
i)
Emergency in-
put active
Check the emergency input (program-
mable via
Simply Connect
).
48
Limit switch fault,
leaf 1
Leaf limit switch fault.
Check the connection of the limit
switches.
49
Limit switch fault,
leaf 2
Leaf limit switch fault.
Check the connection of the limit
switches.
56
(
i)
Battery opera-
tion
The notification remains as long as the
automation is operating on the battery
due to a mains power failure.
60
Maintenance re-
quest
Ask the installer to carry out scheduled
maintenance.
61
Obstacle detected
Leaf1
An obstacle that prevents the leaf from
moving has been detected. Remove
the obstacle.
62
Obstacle detected
Leaf2
as above
63
Intrusion attempt in
progress
An attempt to open the leaf manually
has been detected. Start a movement.
65
SETUP
in progress
SETUP
is in progress. The notification re-
mains as long as the phase is in progress
67
(
i)
Low energy
consumption mode
E124S is operating on battery, in
SLEEP
mode.
70
Battery discharged The charge level of the emergency bat-
tery is too low for the movements to be
carried out.
8
Errors, Alarms, Info
Error
(number on white background) -
Alarm
(number on grey
background) -
Info
(
i
).
00
No notification
01
Board failure
Perform
RESET
. If the problem persists,
replace the E124S.
02
Board thermal pro-
tection
Thermal overload protection active.
Wait for the E124S to cool down.
Check for overloads.
06
Encoder 2 fault
Make sure that the encoder is connected
properly. If the problem persists,
replace the encoder.
07
Motor 1 fault
Motor disconnected or short-circuited.
Check the wiring. If the problem
persists, replace the motor.
08
Motor 2 fault
13
Radio blocked
Presence of radio codes that are not
compatible with the radio module
installed. Delete the radio controls, or
change the type of radio module.
16
Encoder 1 fault
Make sure that the encoder is connected
properly. If the problem persists,
replace the encoder.
20
FAIL-SAFE
test failed
FAIL-SAFE
test of a device failed. Check
the connections, programming, and that
the safety devices are working correctly.
22
Programming data
corrupted
Programming data NOT valid or cor-
rupted. Repeat BUS 2easy program-
ming and the registration.
24
Consecutive obsta-
cles in closing
The programmed number of consecutive
obstacles in closing has been reached.
Remove the obstacle. If the problem
persists, repeat the
SETUP
.
25
LOCK
1 fault
Check the
LOCK
1 connection. Remove
the cause of the short circuit.
30
Flashing light short
circuit / overload
Check the flashing light connection.
31
Consecutive obsta-
cles in opening
The programmed number of consecutive
obstacles in opening has been reached.
Remove the obstacle. If the problem
persists, repeat the
SETUP
.