ADVANCED PROGRAMMING
Display
Advanced Function
cF
0
1 2 4 3
6
5
bo
TIME OF MAXIMUM POWER AT STARTING:
You can set the starting time. During start the motors work at maximum
power for starting the movement.
Adjustable from
00
to
10
sec, in 1-second steps (ignoring the power
level selected with
F1
and
F2
).
Other more detailed programming possibilities are feasible
by programming with a PC (see dedicated instructions).
02
02
02
02
cS
FINAL STROKE WHEN CLOSING (RAM STROKE) (NOT displayed
if function
FC
=
1
):
Lets you enable/disable the ram stroke on swing-leaves.
The ram stroke facilitates latching of the electric lock by activating the
motors at maximum power during final closing.
Y
= enabled (for 2 sec)
no
= disabled
In case of systems with an absolute encoder, to enable this
function a setup must be performed using the automatic
leaf stop on the mechanical contact point.
no
no
no
no
rS
REVERSE STROKE WHEN OPENING displayed if function
FA
=
1
):
Lets you enable/disable the reverse stroke on leaf doors.
The reverse stroke facilitates unlatching of the electric lock. When the
automatic system is closed, before starting to open, the motors give a
brief push to close.
Y
= enabled (for 2 sec)
no
= disabled
In case of systems with an absolute encoder, to enable this
function a setup must be performed using the automatic
leaf stop on the mechanical contact point.
no
no
no
no
EL
ELECTRIC LOCK ON LEAF 2:
The board has a terminal dedicated to the connection of an electric lock.
Normally the electric lock must be connected to leaf 1. If the electric
lock is located on leaf 2, adjust the parameter. This parameter does not
allow the setting
Y
if
Mn
=
2
)
Y
= electric lock on leaf 2
no
= electric lock on leaf 1
no
no
no
no
Od
DELAY FOR OPENING LEAF (visualised only with the function
Mn
=
2
):
You can set the delay time for starting leaf 2 opening with respect to leaf
1, in order to avoid overlapping of the two leaves.
Adjustable from
00
to
59
sec, in 1- second steps.
Next the value 59, the viewing changes to minutes and tenths of a second
(separated by a decimal point) and time is adjusted in 10-second steps up
to the maximum value of
1.3
minutes.
e.g.: if the display shows
1.2
, the time is 1 min and 20 sec.
02
02
02
02
r1
LEAF 1 DECELERATION:
You can adjust the deceleration space as a percentage of the total travel
of leaf 1.
Adjustable from
00
to
99
%, in 1% steps.
00
= no deceleration
01
= minimum deceleration space
99
= maximum deceleration space
30
30
20
30