31
MAN20001512-01-03/22 (translation of the original operating instructions)
Operating Instructions
Key Adapter CKS2-K-BP/BR-CC-FLX
EN
14.3. Error messages
Err
or code via IO-Link
LED indicator
Error
Troubleshooting
Acknowledg-
ing errors
Remove key for 2 s
Reset
Teach-in error
0x1F
¨
white/red
slowly
No key detected during teach-in standby.
The key must be inserted within 3 minutes of the
pushbutton being pressed.
Key removed from the key adapter prior to the end of
the teach-in operation.
Repeat teach-in operation.
0x28
The pushbutton was pressed for too long.
Press the pushbutton for no longer than 30 s.
0x25
blue quickly
Disabled key detected during the teach-in operation:
The key was taught-in during the penultimate teach-in op-
eration and is disabled for the current teach-in operation.
Repeat the teach-in operation with a new key (see
12.2. Teaching-in a new key on page 27)
.
0x42
blue slowly
Invalid key detected:
The key is not intended for the current device configu-
ration.
Ì
Perform the teach-in operation with a key intended
for the current device configuration.
Ì
If the device is to be reconfigured, observe chapter
12.1. Configuring the device and teaching-in the key
.
0x45
blue
Faulty or incompatible key detected:
The key’s data structure cannot be read. The key is
faulty or is not suitable for the device.
Repeat teach-in operation with a new key.
Input error
0x2E
violet slowly
Different signal states at the safety input FI1A or FI1B
during operation.
Ì
Check wiring.
Ì
Check preceding device in the chain.
0x30
Different signal states at the safety inputs FI1A and FI1B
during the self-test.
Check wiring.
0x31
0x32
Ì
Test pulses not detected at safety input FI1A or FI1B
during operation.
Ì
With a single device or the first switch in the switch chain:
different signal states detected at safety inputs FI1A and
FI1B during operation.
Transponder/read error
0x44
blue slowly
Invalid key detected during operation:
The key is not intended for the current device configu-
ration.
Use a valid key.
0x46
blue
Faulty or incompatible key detected during operation:
The key’s data structure cannot be read. The key is
faulty or is not suitable for the device.
-0x47
blue quickly
Disabled key detected during operation:
The key is not the currently valid key.
0x48
¨
white/blue
slowly
Non-taught-in key detected during operation.
Ì
Use the currently valid key.
Ì
Teach-in the key.