10.1. Series connection with wiring in the control cabinet
The series connection can be realized via additional terminals in a control cabinet.
Important!
In case of series connection with IO-Link communication:
Ì
The safety outputs are permanently assigned to the respective safety inputs of the downstream key
adapter. FO1A must be routed to FI1A and FO1B to FI1B.
Ì
If the connections are interchanged (e.g. FO1A to FI1B), the downstream device will enter the fault state.
Safety
Outputs
Monitoring
Output
Safety Inputs
Readhead
Schlüssel/Key:
Safety
Outputs
Monitoring
Output
Safety Inputs
Readhead
Schlüssel/Key:
Safety
Outputs
Monitoring
Output
Safety Inputs
Readhead
Schlüssel/Key:
F-DI 8x24VDC HF
6ES7136-6BA00-0CA0
ET200SP
POWER SUPPLY
6ES7155-6AU00-0BN0
X80
1
2
-F1
UB
2
FI1A
6
FI1B
1
0V
7
OD/C
5
FO1A
3
FO1B
4
n.c
8
-B1
EUC168921
UB
2
FI1A
6
FI1B
1
0V
7
OD/C
5
FO1A
3
FO1B
4
n.c
8
-B2
EUC168921
UB
2
FI1A
6
FI1B
1
0V
7
OD/C
5
FO1A
3
FO1B
4
n.c
8
-B3
EUC168921
1
1L+
2
1M
3
2L+
4
2M
1
DI0
2
DI1
3
DI2
4
DI3
5
DI4
6
DI5
7
DI6
8
DI7
M
L+
9
VS0
10
VS1
11
VS2
12
VS3
13
VS4
14
VS5
15
VS6
16
VS7
24V DC
0 V
24 V DC
0 V
Fig. 2:
Connection example for series connection with wiring in the control cabinet