13
MAN20001512-01-03/22 (translation of the original operating instructions)
Operating Instructions
Key Adapter CKS2-K-BP/BR-CC-FLX
EN
8.4. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì
Use connection components and connecting cables from EUCHNER.
Ì
On the use of other connection components, the requirements in the following table apply. EUCHNER
provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connecting cables:
Parameter
Value
Unit
Conductor cross-section, min.
0.25 … 0.34
mm²
R max.
80
W
/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommended cable type
5-pin
5 x 0.34 mm²
8-pin
LIYY 8 x 0.34 mm²
8.5. Connector assignment of key adapter CKS2-K-BR-CC-FLX-F00-USA-…
with plug connector M12, 8-pin
Plug connector
(view of connection side)
Pin
Designation
Function
Conductor coloring
of connecting
cable
1)
2 1
4
3
8
5
6
7
1
FI1B
Enable input, channel B
WH
2
UB
Operating voltage, 24 V DC
BN
3
FO1A
Safety output, channel A
GN
4
FO1B
Safety output, channel B
YE
5
OD/C
Monitoring output/communication
GY
6
FI1A
Enable input, channel A
PK
7
0V
Ground 0 V DC
BU
8
-
n.c.
RD
1) Only for standard EUCHNER connecting cable
8.6. Connector assignment of key adapter CKS2-K-BP-CC-FLX-F00-USI-…
with plug connector M12, 5-pin
Plug connector
(view of connection side)
Pin
Designation
Function
Conductor coloring
of connecting
cable
1)
1
4
3
2
5
1
UB
Operating voltage, 24 V DC
BN
2
FO1A
Safety output, channel A
WH
3
0V
Ground 0 V DC
BU
4
FO1B
Safety output, channel B
BK
5
-
n.c.
GY
1) Only for standard EUCHNER connecting cable