Manufacturer Specific Profile Area
CAN-CBX-AI420
Manual • Doc.-No.: C.3030.21 / Rev. 1.4
Page 97 of 103
7.11.9 Calibration Gain Value (2405
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
2405
h
0
Number of entries
4
4
unsigned 8
ro
1
Calibration_Gain_1
8000
h
...7FFF
h
Gain
Factory
_1
integer 16
rw
2
Calibration_Gain_2
8000
h
...7FFF
h
Gain
Factory
_2
integer 16
rw
3
Calibration_Gain_3
8000
h
...7FFF
h
Gain
Factory
_3
integer 16
rw
4
Calibration_Gain_4
8000
h
...7FFF
h
Gain
Factory
_4
integer 16
rw
With this object the gain of the A/D-converter channels can be corrected. The gain value, with
which the measured A/D-converter value is multiplied, is calculated as:
Calibration_Gain_x
Gain_x = 1+ ---------------------------
2
18
with x= 1, 2, 3, 4
The resulting value range for the gain factor is: 0.875 ... 1.125
The default values Gain
Factory
_x (x = 1 ...4) are determined during the factory calibration of the
CAN-CBX-AI420. Via object 1011
h
(restore_manufacurer_parameter) these module-specific
default values can be restored.