Manufacturer Specific Profile Area
Manual • Doc.-No.: C.3030.21 / Rev. 1.4
CAN-CBX-AI420
Page 92 of 103
7.11.4 Sample Time Actual Value (2312
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
2312
h
0
Number of entries
2
2
unsigned 8
ro
1
Sample_Time_Actual _1
0...FFFF
h
-
unsigned 16
ro
2
Sample_Time_Actual _2
0...FFFF
h
-
unsigned 16
ro
3
Sample_Time_Actual _3
0...FFFF
h
-
unsigned 16
ro
4
Sample_Time_Actual _4
0...FFFF
h
-
unsigned 16
ro
Via this object the actual value of the preset sample time can be read (refer to notes on sample time
setting on page 89)
Assignment of the variable Sample_Time_Actual_x (x = 1...4):
In the default setting of the objects the sample time [
Ü
s] results from the value of the variable read,
multiplied by 0.5.
Value of the variable
Sample_Time_Actual _x
Actual value of the
sample time
0
0
Ü
s
1
0.5
Ü
s
:
:
FFFF
h
32767.5
Ü