4. Troubleshooting (PROFIBUS DP)
RC700 / RC90 Option Fieldbus I/O Rev.14
297
♦
Causes of Error
Possible Cause
Examination Method
Countermeasure
Disconnected
terminating
resistors
Cable
disconnection
Disconnected
connector
Disconnected
signal wire
(1)
Check that terminating
resistors are connected to
both ends of the network.
(2)
Measure resistance between
signal wires with device
power supply OFF.
→
Normal: 100 to 120
Ω
Measuring point: Connection
of the trouble unit
For details, refer to the section
4.2.3.1 Connection Problem
.
Fix the problem.
How to find the trouble
point:
Remove the terminating
resistor on one end of the
network.
The trouble point is where
resistance changes from 220
Ω
.
Loose connector
Loose signal wire
Check for the connection of
connectors and signal wires.
→
The connectors and signal
wires should be firmly
connected.
Checkpoint: all stations and all
branch taps
For details, refer to the section
4.2.3.2 Loose Connector and
Signal Wire
.
Connect the connectors and
signal wires again.
Electrical surges of
device power
supply
Measure voltage of the device
power supply at the trouble unit.
→
It should be within the range
of sufficient voltage for device
operation.
Check voltage of the device
power supply.
Noise
(external cause)
Check the noise intrusion via the
following paths (1) to (3).
(1)
Noise via shield
(2)
Induced noise via
communication cable
(3)
Device power supply
→
For details, refer to the section
4.2.3.3 Noise Intrusion
.
Take countermeasures
against noise.
Broken unit
Replace the trouble unit with a
new one.
→
Verify whether the problem is
fixed.
Replace the unit with a new
one.
No cause is
identified.
Identify the trouble point by
dividing the network.
→
For details, refer to the section
4.2.3.4 Broken Unit
Examination
.
Summary of Contents for RC700
Page 1: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 EM198C4088F ...
Page 2: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 ...
Page 8: ...vi RC700 RC90 Option Fieldbus I O Rev 14 ...
Page 12: ...Table of Contents x RC700 RC90 Option Fieldbus I O Rev 14 ...
Page 340: ...5 Maintenance Parts List 328 RC700 RC90 Option Fieldbus I O Rev 14 ...