7
1.3.3 General Specifications
PROFIBUS DP Communication Specifications
Item
Specification
Communication
Method
Hybrid
(token passing procedure and master-slave
communication)
Baud Rates
9.6 kbps, 19.2 kbps, 93.75 kbps, 187.5 kbps, 500 kbps,
1500 kbps, 3 Mbps, 6 Mbps, and 12 Mbps.
Transfer Distance
Baud Rates
Cable Length
12 Mbps
6 Mbps
3 Mbps
1500 kbps
500 kbps
187.5 kbps
93.75 kbps
19.2 kbps
9.6 kbps
100 m
100 m
100 m
200 m
400 m
1000 m
1200 m
1200 m
1200 m
Maximum Stations
126 (including master unit and repeater)
Data Length / Frame
244 bytes
Cable
2-wire cable dedicated to PROFIBUS (2 wires for signal)