2. Installation
RC700 / RC90 Option Fieldbus I/O Rev.14
123
4. Select [Fieldbus Slave]-[General].
(4)
(5)
5. Confirm that the following items are displayed.
Fieldbus Type
: PROFIBUS-DP
Node Address
: Configure switch node address
Type
: Byte (default setting)
Input Bytes
: 32 (default setting)
Output Bytes
: 32 (default setting)
6. Click <Close>.
Editing of Configuration
You can change the configuration of PROFIBUS-DP slave module if necessary.
1. Select [Setup]-[System Configuration] and display the [System Configuration] dialog
box.
2. Select [Inputs / Outputs]-[Fieldbus Slave]-[General].
3. Configure a node address.
A node address from 0 to 125 is available for the PROFIBUS-DP device.
Generally, node addresses are
recommended to be configured
as shown in the table.
Node address
Device Name
0
Service unit such as PG/PC
1
Operation panel such as HMI
2
Master station
3-125
DP slave station