Page 33
EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
www.eps-germany.de
PSI 10000 4U Serie
2.3.3
Installing the device
•
Select the location for the device so that the connection to the load is as short as possible.
•
Leave sufficient space, at least 30 cm (1 ft), behind the equipment for ventilation (only required
for the standard air-cooled version)
A device in a 19” chassis will usually be mounted on suitable rails and installed in 19” racks or cabinets. The depth
of the device and its weight must be taken into account. The handles on the front and read are for help with sliding
in and out of the cabinet. Slots on the front plate are provided for fixing the device (fixing screws not included).
The unacceptable positions, as shown below, are also valid for the vertical mount of the device onto a wall or inside
a cabinet. The required air flow would be insufficient. This wouldn’t actually apply to water cooled models, but the
construction of the entire device isn’t made for operation in this position.
Acceptable and unacceptable installation positions (air or water cooled, air cooled shown):
Standing surface