Page 11
EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
www.eps-germany.de
PSI 10000 4U Serie
30 kW
Model 380/400/480 V
PSI 10060-1000
PSI 10080-1000
PSI 10200-420
Resistance regulation
Adjustment range
0.003...5 Ω
0.003...5 Ω
0.165...25 Ω
Accuracy
(1
(at 23 ± 5 °C / 73
±
9 °F) ≤ 0.3% of max. resistance ± 0.1% of maximum current
Display: Resolution
See section
“1.9.6.4. Resolution of the displayed values“
Analog interface
(2
Set value inputs
U, I, P, R
Actual value outputs
U, I
Control signals
DC output on/off, remote control on/off, resistance mode on/off
Status signals
CV, OVP, OCP, OPP, OT, PF, DC on/off
Galvanic isolation to the device
Max. 725 V DC
Insulation
Allowed potential shift (floating voltage) on the DC output:
Negative DC to PE
±500 V DC
±500 V DC
±725 V DC
Positive DC to PE
+600 V DC
+600 V DC
+1000 V DC
AC input <-> PE
2.5 kV DC
AC input <-> DC output
2.5 kV DC
Miscellaneous
Cooling (standard)
Temperature controlled fans, front inlet, rear exhaust
Cooling (WC)
Water
Ambient temperature
0...50 °C (32...133 °F)
Storage temperature
-20...70 °C (-4...158 °F)
Humidity
< 80%, not condensing
Standards
EN 61010-1:2007-11, EN 50160:2011-02
EN 61000-6-2:2016-05, EN 61000-6-3:2011-09
Overvoltage category
2
Protection class
1
Pollution degree
2
Operational altitude
< 2000 m (6500 ft)
Digital interfaces
Featured
1x USB and 1x Ethernet for communication, 1x USB-A for data recording, Mas
-
ter-slave
Slot
Optional: CANopen, Profibus, Profinet, RS232, CAN, EtherCAT
Galvanic isolation from device
Max. 725 V DC
Terminals
Rear side
Share Bus, DC output, AC supply, remote sensing, analog interface, USB, Ethernet
master-slave bus, interface module slot
Front side
USB for sticks
Dimensions
Enclosure (W x H x D)
19“ x 4U x 670 mm (26.4”)
Total (Standard) (W x H x D)
483 x 177 x min. 760 mm (19” x 7” x min. 29.9”)
Weight (standard)
≈ 50 kg (110 lbs)
≈ 50 kg (110 lbs)
≈ 50 kg (110 lbs)
Weight (WC)
(3
≈ 56 kg (123 lbs)
≈ 56 kg (123 lbs)
≈ 56 kg (123 lbs)
Article number (standard)
06230800
06230801
06230802
Article number (WC)
(3
06250800
06250801
06250802
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value. With the resistance, the
accuracy rating already includes the error of the actual resistance display.
(2 For technical specifications of the analog interface see
“3.5.4.3. Analog interface specification“
(3 WC = optional water cooling