10.3 Furnace Specifications
Multi-Fuel Burning Appliance
Model
Number
EL-140H
EL-200H
EL-350H
Bonnet
Capacity
Output BTU
112,000 BTU
160,000 BTU
280,000 BTU
Fuel Input
1.0 GPH
1.4 GPH
2.5 GPH
Nozzle Only
No. 30609-5
No. 30609-5
No. 30609-28
Fuels
ASTM D396 No. 2 Fuel Oil, Used Crankcase Oil, and Used Automatic Transmission Fluid
Designed
Outlet Air
Temperature
250°F Maximum
Flue Draft
-0.05" WC (Minimum 10’ Stack)
Atomizing
Air Pressure
9-11 PSI
Blower Size
9" X 9"
10" X 10"
12” X 9”
Unit Heater
or Ductable
0.28" WC Maximum External Static Pressure
Maximum
Fuse Size
25A
Blower
Motor
1/3 HP, 115V/60Hz, 6.1A
1/2 HP, 115V/60Hz, 8.1A
1 HP, 115V/60Hz, 11.8A
Burner
Motor
1/5 HP, 115V/60Hz, 3.3A
1/5 HP, 115V/60Hz, 3.3A
1/5 HP, 115V/60Hz, 3.3A
Metering
Pump Motor
15Watt, 115V/60Hz, 0.35A
Ignition
Transformer
& Control
Circuit
115V/60Hz, 2.0A
Oil
Preheaters
115V/60Hz, 2.0A Maximum
115V/60Hz, 2.5A Maximum
115V/60Hz, 3.0A Maximum
Minimum
Clearance to
Combustible
Surfaces
Top - 6"
Front - 24"
Sides - 6"
Rear - 6"
Flue Pipe - 18"
Bottom - 6"
Warm air duct within 3' of furnace (when ducted) - 6"
For commercial and industrial use only.
In buildings where gas vapors may be present, the furnace must be mounted at least 8’ above the floor.
The furnace may be suspended from the ceiling.
Normal continuous sound level: 77dBA
86
Call 1-615-471-5290 for Technical Support
Summary of Contents for EL-140H
Page 2: ......
Page 51: ...45 Call 1 615 471 5290 for Technical Support ...
Page 90: ...10 2 Carlin 50200E Primary Control 84 Call 1 615 471 5290 for Technical Support ...
Page 91: ...85 Call 1 615 471 5290 for Technical Support ...
Page 93: ...87 Call 1 615 471 5290 for Technical Support ...
Page 94: ...88 Call 1 615 471 5290 for Technical Support ...
Page 95: ...89 Call 1 615 471 5290 for Technical Support ...