3. What was in the recently added
fuel?
Standard Mix - Go to Next
Action/Question/Component
Unknown/Cold/New Oil/Non Standard Mix -
Call EnergyLogic Technical Services group for
an Oil Analysis to be performed
4. When was the tank last drained of
water and other fall out materials?
Used Oil Storage Tanks should be drained on
an annually from the bottom most drain port
until only oil flows from the tank
5. When was the oil last analyzed?
EnergyLogic recommends that an oil analysis
be performed annually
6. Analysis Results (If EL does not
have the results, could we get them)
Consult EnergyLogic Technical Services group
for oil analysis interpretation
Heat
Exchanger
1. Clean Heat Exchanger and Flue:
See Heat Exchanger Cleaning in
Section 8.5.1.
The entire furnace should be maintained and
clean every 800 to 1000 run hours
Pump/Filter
1. Check Fuel Pump Motor. Is the
fuel pump motor running while the
burner is running?
Yes - Go to Next Action/Question/Component
No - See Metering Pump Assembly Testing in
Section 9.3
2. Check Fuel Pressure: Turn
furnace on or reset the red button of
the primary control. What is the fuel
pressure reading (gauge at pump
outlet-PSI) while burner is running?
0 or erratically fluctuating then Go to
Action/Question 4, or greater than 20 psi, see
Nozzle/Solenoid cleaning, or between 3 and
15 (normal) go to Component
3. Fuel line check. Do the fuel lines
contact an exterior/cold wall?
Yes - If fuel line is in contact with an exterior
wall, this could result in extra load on the
pump. If fuel line is cold, add spacers (at least
.5 inches) to eliminate contact with the exterior
wall
No - Go to Next Action/Question
4. Check Fuel Vacuum: Turn furnace
on or reset the red button of the
primary control. What is the fuel
vacuum reading (gauge at pump inlet-
inches Hg) during the time the burner
is running?
Zero or erratically fluctuating then Go to Next
Action/Question, or 1 to 10 In./Hg then Go to
Action/Question 6, or 10 in./Hg or higher (for
more vertical suction distance, allow more
vacuum) then Replace oil filter -see filter
replacement. If you are using a non-
EnergyLogic tank with strainer, inspect the
strainer for debris.
5. See Metering Pump Assembly
Testing Procedure in Section 9.3
If Metering Pump Assembly Tested Good, go
to next Component. Otherwise repair/replace
necessary components.
67
Call 1-615-471-5290 for Technical Support
Summary of Contents for EL-140H
Page 2: ......
Page 51: ...45 Call 1 615 471 5290 for Technical Support ...
Page 90: ...10 2 Carlin 50200E Primary Control 84 Call 1 615 471 5290 for Technical Support ...
Page 91: ...85 Call 1 615 471 5290 for Technical Support ...
Page 93: ...87 Call 1 615 471 5290 for Technical Support ...
Page 94: ...88 Call 1 615 471 5290 for Technical Support ...
Page 95: ...89 Call 1 615 471 5290 for Technical Support ...