52
ESE 904 - 1304 DBG DIN
Status: at
January 2013
Symbol
Result
Significance
lights up red
Circuit breaker jumps to Pos. 0 and
the generator cuts out
Insulation monitoring is OK
stays off
Circuit breaker stays in Pos. 1 and
the generator continues to run
Insulation monitoring is defective
Table 5.4: Insulation monitoring plus switching off
The insulation monitoring test has been run.
4. The reset button
(see Fig. 5-2-(2))
must be pressed after
switching off and the circuit breaker must be turned
back to Pos. 1 so that the unit can be used again.
1. Plug in the consumer and switch on.
The displayed symbol (see
Fig. 4-6-(8))
and the position of
the circuit breaker indicate the result:
Symbol
Significance
lights up red
Insulation fault (
≤
23 k
Ω
)
Yellow
Insulation fault (
≤
34.5 k
Ω
)
stays off
Connected unit is OK
Table 5.5: Insulation monitoring whilst running without switching off
If an insulation fault exists and the unit was previously
OK when tested without a device connected (see above),
the insulation fault has been caused by the device.
2. After the device has been switched off and unplugged,
the circuit breaker must be returned to Pos. 1, and the
generator must be restarted, in order for the device to be
operated again.
Insulation monitoring
whilst running:
Summary of Contents for ESE 1104 DBG ES FS DIN
Page 10: ...General information 10 ESE 904 1304 DBG DIN Status at January 2013 Notes...
Page 24: ...24 ESE 904 1304 DBG DIN Status at January 2013 Notes...
Page 31: ...Status at January 2013 ESE 904 1304 DBG DIN 31 Notes...
Page 47: ...Status at January 2013 ESE 904 1304 DBG DIN 47 Notes...
Page 75: ...Status at January 2013 ESE 904 1304 DBG DIN 75 Notes...
Page 79: ...Status at January 2013 ESE 904 1304 DBG DIN 79 Notes...