78
ESE 904 - 1304 DBG DIN
Status: at
January 2013
Designation
Value
Unit
Setting up height above sea
level
< 100
[m]
Temperature
< 25
[°C]
Relative air humidity
< 30
[%]
Table 8.2: Ambient conditions for the generator
Output reduction
for each addi-
tional
Unit
1 %
100
[m]
4 %
10
[°C]
Table 8.3: Generator performance reduction dependent on the ambient
conditions
Line
max. line length
Unit
HO 7 RN-F (NSH öu) 1.5 mm
2
60
[m]
HO 7 RN-F (NSH öu) 2.5 mm
2
100
[m]
Table 8.4: Maximum line length of the distribution network as a function of
the cable cross-section
The general limitation of 100 m for the overall length was
selected in the interest of safe handling during practical
use. Larger dimensioning of the distribution network is
only to be undertaken by a qualified electrician or
trained personnel.
Ambient conditions
Reduced output
Distribution network