Function group
BATCHING
Introduction
The “BATCHING” function group together with the preset totalizer enables simple batching cycles to
be controlled. The Promag 33 transmitter has two relays which can be used for controlling single or
two-stage batching cycles:
Entering a compensation quantity can compensate for
plant-specific but constant
errors in volume
e.g. caused by after-runs of pumps, closing time of valves, etc.
Note!
•
For short-cycle batching (filling time < 20 s)
→
see function “SELF CHECKING” (page 78)
•
If a system error (failure) occurs during a batching cycle or an empty pipe is detected (EPD)
the filling procedure is immediately stopped.
Starting / Stopping a Batching Cycle
The batching cycle can be started and stopped in four different ways:
•
via the HART interface or Rackbus 485
•
via the auxiliary input (with the “RS 485” communications module only)
•
via the function “BATCHING”
•
from the HOME position. Starting the batching cycle from the HOME position is always
possible if the “BATCH VARIABLE” function is set to “VOLUME” (see next page):
6
START – STOP – CANCEL
(
1
confirms the selection)
Note!
If a batching variable is activated, the “BATCHING” function group is first shown on the display when
entering the operating matrix. The function “BATCH QUANTITY” then moves into the first position within
this function group. This makes using the matrix much easier for the user. In addition all batching func-
tions can be changed without entering a code number.
Q
t
t
Q
Single-stage batching cycle
Relay 1
Relay 2
switch points
Batch quantity
After-run
Two-stage batching cycle (with pre-batch contact of relay 1)
Fine batching
Coarse batching
Switch point
Relay 2
ba009
y
7
2
After-run
Note!
Note!
Promag 33
6 Description of Functions
Hauser
63
Summary of Contents for PROMAG 33
Page 43: ...Promag 33 5 Display and Operation Endress Hauser 43...
Page 46: ...5 Display and Operation Promag 33 46 Endress Hauser...
Page 84: ...6 Description of Functions Promag 33 84 Endress Hauser...
Page 98: ...7 Trouble shooting Maintenance and Repairs Promag 33 98 Endress Hauser...
Page 106: ...8 Dimensions Promag 33 106 Endress Hauser...
Page 116: ...9 Technical Data Promag 33 116 Endress Hauser...
Page 125: ......