Connection diagram for the transmitter (“RS 485”)
3
28
20
21
23
24
25
26
27
1
2
22
+
-
+
-
+
-
+
-
1
2
3
28
20
21
22
23
24
25
26
27
Supply cable
Ground terminal for
protective conductor
Ground terminal for
signal cable shield
Signal cable
ba009y32
Fuse
•
Power supply 20...55 V AC / 16...62 V DC:
2.5 A slow-blow / 250 V; 5.2
×
20 mm
•
Power supply 85...260 V AC:
1 A slow-blow / 250 V; 5.2
×
20 mm
Ground connection (protective earth)
L1
for AC power supply
L+
for DC power supply
N
L–
Alarm output (Relay 1): can be configured
max. 60 V AC / 0.5 A AC; max. 30 V DC / 0.1 A DC
Ground connection (screening of signal cable)
Version with a “RS 485” communication module
Status output (Relay 2): can be configured
max. 60 V AC / 0.5 A AC; max. 30 V DC / 0.1 A DC
RS 485 interface
or *
Auxiliary input
A
+ / –
3...30 V DC
B
– / +
Current output (active): 0/4...20 mA, R
L
< 700
Ω
or *
Pulse/frequency output (active/passive): f
max
= 10 kHz
active: 24 V DC, 25 mA (max. 250 mA/20 ms)
passive: 30 V DC, 250 mA
* Only one version is possible for each, depending on the setting selected in
the function “SYSTEM CONFIG.” (see page 71).
The input and outputs are galvanically isolated from the power supply and
from each other.
Fig. 23
Terminal compartment
Promag 33 (RS 485)
4 Electrical Connection
Promag 33
24
Hauser
Summary of Contents for PROMAG 33
Page 43: ...Promag 33 5 Display and Operation Endress Hauser 43...
Page 46: ...5 Display and Operation Promag 33 46 Endress Hauser...
Page 84: ...6 Description of Functions Promag 33 84 Endress Hauser...
Page 98: ...7 Trouble shooting Maintenance and Repairs Promag 33 98 Endress Hauser...
Page 106: ...8 Dimensions Promag 33 106 Endress Hauser...
Page 116: ...9 Technical Data Promag 33 116 Endress Hauser...
Page 125: ......