Maximum measured error
t-mass 65F and t-mass 65I
±1.5 % of reading for 100 % to 10 % of range (at reference conditions)
±0.15 % of full scale for 10 % to 1 % of range (at reference conditions)
A0021682
Fig. 52:
Maximum measured error (% mass flow) as % of full scale value, see next table
0
1
0
[% kg/h]
±
1
0
0
50
80
[%]
90
1
00
±5
±
1
5
2
0
3
0 40
60 70
±
2
0
11
0
12
0
13
0
1
40
1
50
[% lb/h]
Order code for "Calibration
flow" (not verified)
Performance characteristics
Description
G
Q = 100 to 150 %:
±1.5 to ±5 % of the current
measured value increasing
linearly as expressed in the
following equation:
±1.5 ± (X
n
-100) × 0.07[% o.r.]
(100 % < X
n
≤
150 %; X
n
= current
flow in % o.f.s.)
Q = 10 to 100 % of full scale value
±1.5 % o.r.
Q = 1 to 10 % of full scale value
±0.15 % o.f.s.
(all data under reference
conditions)
Factory calibration:
The measuring device is calibrated
and adjusted on an accredited and
traceable calibration rig and its
accuracy is certified in a calibration
report (3 control points).
H
Q = 100 to 150 %:
±1.5 to ±5 % of the current
measured value increasing
linearly as expressed in the
following equation:
±1.5 ± (X
n
-100) × 0.07[% o.r.]
(100 % < X
n
≤
150 %; X
n
= current
flow in % o.f.s.)
Q = 10 to 100 % of full scale value
±1.5 % o.r.
Q = 1 to 10 % of full scale value
±0.15 % o.f.s.
(all data under reference
conditions)
Factory calib flow
conditioner
:
The measuring device is calibrated
and adjusted on an accredited and
traceable calibration rig with a flow
conditioner and its accuracy is
certified in a calibration report (3
control points).