Proline t-mass 65 PROFIBUS DP/PA
Commissioning
Hauser
61
5.
Configuration of the Analog Input function blocks 1 to 3:
The measuring device has three Analog Input function block (AI modules), through
which the various measured variables can be cyclically transmitted to the PROFIBUS
Master (class 1). The assignment of a measured variable to the Analog Input function
block is shown below using the example of Analog Input function block 1 (AI module,
slot 1).
Using the CHANNEL function, it is possible to determine the measured variable (e.g.
mass flow) to be cyclically transmitted to the PROFIBUS Master (class 1):
a. Select COMMUNICATION
BLOCK SELECTION
b. Select the option AI1 - OUT VALUE
c. Go to the function CHANNEL
d. Select the option MASS FLOW
6.
Configuration of totalizers 1 to 2:
The measuring device has two totalizers. The following example describes the configu-
ration of the totalizer using totalizer 1 as an example.
Using the CHANNEL function, it is possible to determine the measured variable (e.g.
totalized mass flow) to be cyclically transmitted to the PROFIBUS Master (class 1) as a
totalizer value:
a. Select TOTALIZER
SELECT TOTALIZER
b. Select the option TOTALIZER 1
c. Go to the function CHANNEL
d. Select the option MASS FLOW
• Enter the desired unit for the totalizer:
TOTALIZER
UNIT TOTALIZER
• Configure totalizer status (e.g. totalize):
TOTALIZER
SET TOTALIZER
Option: TOTALIZE
• Set the totalizer mode: TOTALIZER
MODE TOTALIZER
Select one of the following options:
– BALANCE (factory setting): calculates the positive and negative flow portions.
– POSITIVE: calculates the positive flow portions.
– NEGATIVE: calculates the positive flow portions.
– HOLD VALUE: The totalizer remains at the last value.
Measured variable
ID for CHANNEL function
MASS FLOW (factory setting AI function block 1)
277
CORR. VOLUME FLOW (factory setting AI function block 2)
398
TEMPERATURE (factory setting AI function block 3)
285
!
Note!
If, when the PROFIBUS network configuration, the module "AI" was integrated in slot 1, 2 or 3, the mea-
sured variable selected in the CHANNEL function is transmitted cyclically to the PROFIBUS Master (class 1)
for the respective Analog Input function block 1 to 3 (PROFIBUS DP
67, PROFIBUS PA
76).
Totalizer value/measured variable
ID for CHANNEL function
MASS FLOW (factory setting totalizer 1 to 2)
277
CORR. VOLUME FLOW
398
OFF
0
!
Note!
If, during the PROFIBUS network configuration, the module or the function "TOTAL" was integrated in slot
4 or 5, the measured variable selected in the CHANNEL function is transmitted cyclically to the PROFIBUS
Master (class 1) for the respective totalizer 1 to 2 (PROFIBUS DP
76).