10 Technical data
Proline Prowirl 72
62
E Hauser
Cable specification
• Permitted temperature range: –40 °C...(max. ambient temperature plus 10 °C)
• Remote version
→
Page 22
Power supply failure
• Totalizer stops at the last value determined (can be configured).
• All settings are kept in the EEPROM.
• Error messages (incl. value of operated hours counter) are stored.
10.1.6
Performance characteristics
Reference operating
conditions
Error limits following ISO/DIN 11631:
• 20...30 °C
• 2...4 bar
• Calibration rig traced to national standards.
• Calibration with the correlatively process connection of the accordingly norms.
Maximum measured error
• Liquid:
< 0.75% o.r. for Re > 20,000
< 0.75% o.f.s for Re between 4,000...20,000
• Gas/steam:
< 1% o.r. for Re > 20,000
< 1% o.f.s for Re between 4,000...20,000
o.r. = Of reading
o.f.s = Of full scale
Re = Reynolds number
Repeatability
±0.25% o.r. (of reading)
Reaction time/
step response time
If all configurable functions are set to 0, you must reckon with a reaction time/step response time
of 200 ms for vortex frequencies as of 10 Hz.
For other settings, a reaction time/step response time of 100 ms must be added to the total filter
reaction time for vortex frequencies as of 10 Hz.
→
Page 99: FLOW DAMPING
Influence of ambiente tempe-
rature
Current output (additional error, in reference to the span of 16 mA):
• Zero point (4 mA)
average T
k
: 0.05%/10 K, max. 0.6% over the entire temperature range –40 °C ... +80 °C
• Span (20 mA):
average T
k
: 0.05%/10 K, max. 0.6% over the entire temperature range –40 °C ... +80 °C
Digital outputs (pulse output, PFM, HART)
Due to the digital measuring signal (vortex pulse) and further digital processing, there is no
interface-related error from changing ambient temperature.
10.1.7
Operating conditions: installation
Installation instructions
see Page 12 ff.
Inlet and outlet run
see Page 14 ff.
Summary of Contents for Proline Prowirl 72
Page 4: ...QUICK SETUP for quick commissioning Proline Prowirl 72 4 Endress Hauser...
Page 20: ...3 Installation Proline Prowirl 72 20 Endress Hauser...
Page 42: ...6 Commissioning Proline Prowirl 72 42 Endress Hauser...
Page 44: ...7 Maintenance Proline Prowirl 72 44 Endress Hauser...
Page 114: ...www endress com worldwide BA084D 06 en 12 05 71008404 FM SGML 6 0...