Proline Prowirl 72
9 Trouble-shooting
E Hauser
47
9
Trouble-shooting
9.1
Trouble-shooting instructions
Always start trouble-shooting with the checklists below if faults occur after start-up or during
operation. This takes you directly (via various queries) to the cause of the problem and the
appropriate remedial measures.
Check the display
No display visible and no output
signals present
1.
Check supply voltage
→
terminal 1, 2
2.
Electronics defective
→
order spare part
→
Page 53
No display visible but output
signals are present
1.
Check whether the ribbon-cable connector of the display module is correctly
plugged into the amplifier board
→
Page 54
2.
Display module defective
→
order spare part
→
Page 53
3.
Electronics defective
→
order spare part
→
Page 53
Display texts are in a foreign
language.
Switch off power supply. Press and hold down both the +/– keys and switch on the
measuring device again. The display text will appear in English and is displayed at
50% contrast.
Measured value indicated, but
no signal output at the current
or pulse output
Electronics board defective
→
order spare part
→
Page 53
▼
Error messages on display
Errors which occur during commissioning or measuring operation are displayed immediately. Error messages consist of
a variety of icons. The meanings of these icons are as follows (example):
– Type of error:
S
= System error,
P
= Process error
– Error message type:
$
= Fault message,
!
= Notice message
–
DSC SENS LIMIT
= Error designation (device being operated near application limits)
–
03:00:05
= Duration of most recent error occurrence (in hours, minutes and seconds), display format - see
OPERATION HOURS function on Page 103
–
#395
= Error number
"
Caution!
• Please refer also to the information on Page 30 ff.!
• The measuring system interprets simulations and positive zero return as system errors, but displays them as notice
messages only.
▼
Other errors (without error message)
Some other error has occurred.
Diagnosis and remedial measures
→
Page 50
Summary of Contents for Proline Prowirl 72
Page 4: ...QUICK SETUP for quick commissioning Proline Prowirl 72 4 Endress Hauser...
Page 20: ...3 Installation Proline Prowirl 72 20 Endress Hauser...
Page 42: ...6 Commissioning Proline Prowirl 72 42 Endress Hauser...
Page 44: ...7 Maintenance Proline Prowirl 72 44 Endress Hauser...
Page 114: ...www endress com worldwide BA084D 06 en 12 05 71008404 FM SGML 6 0...