Commissioning
Proline Promag P 500 HART
100
Hauser
0/4 mA value
20 mA value
Current span
Failure mode
Failure value
Parameter overview with brief description
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Terminal number
–
Shows the terminal numbers
used by the current input
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Signal mode
The measuring device is
not
approved for use in the
hazardous area with type of
protection Ex-i.
Select the signal mode for the
current input.
• Passive
• Active
Active
0/4 mA value
–
Enter 4 mA value.
Signed floating-point
number
0
20 mA value
–
Enter 20 mA value.
Signed floating-point
number
Depends on country
and nominal
diameter
Current span
–
Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
• 0...20 mA
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
Failure mode
–
Define input behavior in alarm
condition.
• Alarm
• Last valid value
• Defined value
Alarm
Failure value
In the
Failure mode
parameter, the
Defined value
option is selected.
Enter value to be used by the
device if input value from
external device is missing.
Signed floating-point
number
0
*
Visibility depends on order options or device settings
10.4.6 Configuring the current output
The
Current output
wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
‣
Current output 1 to n
Terminal number