background image

26127-5-0111

Page 5

REqUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part for 

residential  purposes,  including  those  owned  or  operated  by  the 

Commonwealth and where the side wall exhaust vent termination 

is less than seven (7) feet above finished grade in the area of the 

venting, including but not limited to decks and porches, the following 

requirements shall be satisfied:

1.  INSTALLATION OF CARBON MONOXIDE DETECTORS. At 

the time of installation of the side wall horizontal vented gas fu-

eled equipment, the installing plumber or gasfitter shall observe 

that a hard wired carbon monoxide detector with an alarm and 

battery back-up is installed on the floor level where the gas 

equipment is to be installed. In addition, the installing plumber 

or gasfitter shall observe that a battery operated or hard wired 

carbon monoxide detector with an alarm is installed on each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services 

of qualified licensed professionals for the installation of hard 

wired carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery back-up may be installed on the next adjacent floor 

level.

 

b.  In the event that the requirements of this subdivision can not 

be met at the time of completion of installation, the owner 

shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said 

thirty (30) day period, a battery operated carbon monoxide 

detector with an alarm shall be installed.

2.  APPROVED CARBON MONOXIDE DETECTORS. Each carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified. 

3.  SIGNAGE. A metal or plastic identification plate shall be per

-

manently mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the 

exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, 

“gAS VENT DIRECTLY 

BELoW. KEEP CLEAR oF ALL oBSTRUCTIonS”.

4.  INSPECTION. The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

 

(b)  EXEMPTIONS: The following equipment is exempt from 

248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The equipment listed in Chapter 10 entitled “Equip-

ment Not Required To Be Vented” in the most current 

edition of NFPA 54 as adopted by the Board; and 

 

 

2.  Product Approved side wall horizontally vented gas 

fueled  equipment  installed  in  a  room  or  structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes. 

 

(d)  MANUFACTURER  REQUIREMENTS  -  GAS  EQUIP

-

MENT VENTING SYSTEM NOT PROVIDED. When the 

manufacturer of a Product Approved side wall horizontally 

vented gas fueled equipment does not provide the parts 

for venting the flue gases, but identifies “special venting 

systems”, the following requirements shall be satisfied by 

the manufacturer:

 

 

1.  The referenced “special venting system” instructions 

shall  be  included  with  the  appliance  or  equipment 

installation instructions; and

 

 

2.  The “special venting systems” shall be Product Ap-

proved  by  the  Board,  and  the  instructions  for  that 

system shall include a parts list and detailed installa-

tion instruction.

 

(e)  A copy of all installation instructions for all Product Approved 

side  wall  horizontally  vented  gas  fueled  equipment,  all 

venting instructions, all parts lists for venting instructions, 

and/or all venting design instructions shall remain with the 

appliance or equipment at the completion of the installa-

tion. 

Summary of Contents for DVP30CA30BN-2

Page 1: ...DVP30CA30 B F M S W N 2 DVP30CA30 B F M S W P 2 Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not tr...

Page 2: ...Framing and Finishing 17 18 Horizontal Termination 18 Vertical Termination 19 20 Log Placement 21 Operating Guidelines 22 Lighting Instructions 23 Pilot Flame Characteristics 24 Main Burner Flame Cha...

Page 3: ...e is tempered glass If the glass is cracked or damaged in any way it should be replaced only with a complete glass frame assembly from Empire See parts list on Page 30 for ordering Do not use this fir...

Page 4: ...s Theodorantinescapedgascanadsorborabsorbontoorintowalls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stra...

Page 5: ...visions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be per manently mounted to the exterior of the building at a min...

Page 6: ...enced in such work familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction The installation must conform with local codes or in the absen...

Page 7: ...6DVA E90B DVKVP Direct Vent Kit for Vertical Run 2 46DVA 48B 46DVA DC 46DVA F6 46DVA SC 46DVA FS 46DVA VCH Accessories TMV Millivolt Wall Thermostat Reed Switch FRBC Battery Operated Remote Control FR...

Page 8: ...near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect When using cop...

Page 9: ...ngle to Wall 4 101 6 mm Floor 0 0 mm Installation on Rugs and Tile This appliance must be installed on a flat solid continuous surface e g wood metal concrete This may be the floor or it may be raised...

Page 10: ...e restrictor plate must be used above 10 feet Maximum horizontal run from appliance outlet 12 feet 3 66 m Maximum vertical rise and horizontal run is a combined total of 25 feet 7 62 m Maximum elbows...

Page 11: ...e side and bottom Cutting the Hole Figure 7 After the appliance has been positioned in its permanent location the hole through the exterior wall of the house can be cut This hole needstobe10 highx10 w...

Page 12: ...de 2 Remove cast iron front and carefully set aside 3 Carefully remove glass door 4 Remove the log shelf by removing the 2 screws securing the log shelf to the wall 5 Loosen the upper 2 screws of both...

Page 13: ...ack down locking the air shutter in place Be sure that the air shutter is the same distance from the burner orifice on both sides of the air shutter for proper burner fit up 10 Carefully replace the b...

Page 14: ...ing Routes and Components Important It is always best to locate the appliance in such a way that minimizes the number of offsets and horizontal vent length Sinceitisveryimportantthattheventingsystemma...

Page 15: ...e center line of the regulator I Clearance to service regulator vent outlet 6 feet 1 83 m minimum J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other ap...

Page 16: ...hes The vent pipe is now locked together Continue adding components per the pre planned vent system configuration Be certain that each succeeding vent component is securely fitted and locked into the...

Page 17: ...hole previously cut Secure with nails or screws Continue the vent run through the firestops See Figure 19 Figure 19 Vertical runs of this system which pass through ceilings require the use of ONE 1 ce...

Page 18: ...ews provided Before attachment of the termination run a bead of silicone sealant rated above 250 F on its outside edge too so as to make a seal to that exterior wall NOTE Wood screws can and should be...

Page 19: ...e as follows 1 Check areas of the venting system which are exposed to the elements for corrosion These will appear as rust spots or streaks and in extreme cases holes These components should immediate...

Page 20: ...materials including insulation to the vent system are maintained Vertical Through the Roof Applications Your Gas Fireplace has been approved for a Vertical installations up to 25 feet of vent run b Tw...

Page 21: ...toe resting on the groove in the left front log 12 Place right twig onto right side pin on rear log with toe resting all the way to the right on the right front log 13 Align and place top of glass fr...

Page 22: ...g Pilot Operation 1 FollowtheSAFETYandLIGHTINGINSTRUCTIONSforstanding pilot controls found in this manual and on labels found attached to the appliance CAUTION During the initial purging and subsequen...

Page 23: ...which must be lighted by hand When lighting the pilot follow these instructions exactly B Before lighting smell all around the appliance area for gas Be sure to smell next to the floor because some g...

Page 24: ...thermopile just below the tip A slight yellow flame may occur where the pilot flame and main burner flame meet The incorrect pilot flame is not touching the thermocouple or thermopile This will cause...

Page 25: ...pointment theservicepersonshouldcleandust lint and any light accumulation from the logs and the firebox area An extra soft brush should be used on the logs as they are extremely fragile a vacuum clean...

Page 26: ...ess the black and green wires female push ons attach to the gas valve An additional green wire and the red wire which are stripped and bare will attach to the 750 millivolt wall thermostat accessory o...

Page 27: ...26127 5 0111 Page 27 Wiring Diagram Figure 34 WIRING continued...

Page 28: ...ce glass frame assembly on a non abrasive surface The exterior of the glass frame assembly should be facing the non abrasive surface 7 Insert a putty knife between glass and bottom corners on frame Ca...

Page 29: ...h the pilot lit and the ON OFF switch in the OFF position Replace the faulty thermopile if the reading is below the specified minimum With the pilot in the ON position disconnect the thermopile leads...

Page 30: ...URNER ASSEMBLY 19 P 253 ORIFICE ANGLED FITTING 20 24429 ORIFICE HOLDER BRACKET 21 R 7572 JAMB NUT 22 P 244 ORIFICE 33 LPG 22 P 185 ORIFICE 52 NAT 23 26561 AIR SHUTTER BRACKET 24 23939 FIREBOX BOTTOM 2...

Page 31: ...26127 5 0111 Page 31 PARTS VIEW 1 9 4 2 3 4 6 4 8 10 11 12 14 15 16 28 29 31 36 37 38 39 40 41 42 43 44 45 30 17 18 19 20 21 22 24 25 26 27 32 34 35 23 13 33 5 7 29 47 9 46...

Page 32: ...IGHT 8 R 9694 CASTING DOOR LEFT 9 24191 FIREBOX SUPPORT BRACKET 2 REQUIRED 11 R 9549 CASTING LEG B 12 R 9548 CASTING LEG A PORCELAIN BLACK 1 R 9570 TOP INSERT RIGHT 2 R 9569 TOP INSERT LEFT 3 R 9568 C...

Page 33: ...26127 5 0111 Page 33 1 2 8 3 4 5 6 7 9 9 10 10 10 10 12 11 11 12 CASTING PARTS VIEW...

Page 34: ...to casting before fully tightening bolts as shown in Figure 37 9 Replace cast iron or stone inlay inserts into casting top Note Be sure to remove side shelf supports prior to removing cast iron top t...

Page 35: ...1 4 push on terminal from white wire on the fan control to the ON bottom tab on the switch 9 Insert AUTO OFF ON switch into rectangular notch on wire channel left 10 Install rheostat through hole in...

Page 36: ...y grounded three prong receptacle Do not cut or remove the grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wire for grounding can be purchased plugged...

Page 37: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 38: ...26127 5 0111 Page 38 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 39: ...ng the front of the direct vent fireplace the minimum clearances to combustible construction material are the following Top of appliance ceiling 36 inches Heater Corners 45 angle to Wall 4 inches Rear...

Page 40: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: