background image

26127-5-0111

Page 8

Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/

CGA-B149 (.1 or .2) installation code.

Note:

 Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flexible 

appliance connector cannot exceed three feet in length.

Figure 1

Installing a New Main gas Cock

Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

NOTE:

 The gas control is equipped with a captured screw type 

pressure test point, therefore it is not necessary to provide a 1/8" 

test point up stream of the control.
A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect.

When using copper or flex connector use only approved fittings. 

Always provide a union

 so that gas line can be easily disconnected 

for burner servicing. 

The appliance and it's individual shut off valve must be disconnected 

from supply piping system during any pressure testing of that system 

at test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system 

by closing its individual manual shut off valve during any pressure 

testing of the gas supply piping system at test pressures equal to 

or less than 1/2 psig (3.5 kPa).

Attention!

 If one of the procedures results in pressures in excess of 

1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result 

in a hazardous condition.

Checking Manifold Pressure

Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 

regulator in the gas valve.  Natural gas models will have a manifold 

pressure of approximately 3.5" w.c. (.871 kPa) for maximum input or 

1.7" w.c. (.423 kPa) for minimum input at the valve outlet with the inlet 

pressure to the valve from a minimum of 5.0" w.c. (1.245 kPa) for the 

purpose of input adjustment to a maximum of 10.5" w.c. (2.615 kPa).  

Propane gas models will have a manifold pressure approximately 

10.0" w.c. (2.49 kPa) for maximum input or 5.9" w.c. (1.469 kPa) 

for minimum input at the valve outlet with the inlet pressure to the 

valve from a minimum of 11.0" w.c. (2.739 kPa) for the purpose of 

input adjustment to a maximum of 13.0" w.c. (3.237 kPa). 
A 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge 

connection, is located on the outlet side of the gas control.

gAS SUPPLY

Recommended gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7 mm

3/8”

9.5 mm

1/2”

12.7 mm

3/8”

9.5 mm

10-40 feet

4-12 meters

1/2”

12.7 mm

1/2”

12.7 mm

5/8”

15.9 mm

1/2”

12.7 mm

40-100 feet

13-30 meters

1/2”

12.7 mm

1/2”

12.7 mm

3/4”

19 mm

1/2”

12.7 mm

100-150 feet

31-46 meters

3/4”

19 mm

1/2”

12.7 mm

7/8”

22.2 mm

3/4”

19 mm

1/2 NPT

NIPPLE

1/2 NPT

NIPPLE

Summary of Contents for DVP30CA30BN-2

Page 1: ...DVP30CA30 B F M S W N 2 DVP30CA30 B F M S W P 2 Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not tr...

Page 2: ...Framing and Finishing 17 18 Horizontal Termination 18 Vertical Termination 19 20 Log Placement 21 Operating Guidelines 22 Lighting Instructions 23 Pilot Flame Characteristics 24 Main Burner Flame Cha...

Page 3: ...e is tempered glass If the glass is cracked or damaged in any way it should be replaced only with a complete glass frame assembly from Empire See parts list on Page 30 for ordering Do not use this fir...

Page 4: ...s Theodorantinescapedgascanadsorborabsorbontoorintowalls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stra...

Page 5: ...visions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be per manently mounted to the exterior of the building at a min...

Page 6: ...enced in such work familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction The installation must conform with local codes or in the absen...

Page 7: ...6DVA E90B DVKVP Direct Vent Kit for Vertical Run 2 46DVA 48B 46DVA DC 46DVA F6 46DVA SC 46DVA FS 46DVA VCH Accessories TMV Millivolt Wall Thermostat Reed Switch FRBC Battery Operated Remote Control FR...

Page 8: ...near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect When using cop...

Page 9: ...ngle to Wall 4 101 6 mm Floor 0 0 mm Installation on Rugs and Tile This appliance must be installed on a flat solid continuous surface e g wood metal concrete This may be the floor or it may be raised...

Page 10: ...e restrictor plate must be used above 10 feet Maximum horizontal run from appliance outlet 12 feet 3 66 m Maximum vertical rise and horizontal run is a combined total of 25 feet 7 62 m Maximum elbows...

Page 11: ...e side and bottom Cutting the Hole Figure 7 After the appliance has been positioned in its permanent location the hole through the exterior wall of the house can be cut This hole needstobe10 highx10 w...

Page 12: ...de 2 Remove cast iron front and carefully set aside 3 Carefully remove glass door 4 Remove the log shelf by removing the 2 screws securing the log shelf to the wall 5 Loosen the upper 2 screws of both...

Page 13: ...ack down locking the air shutter in place Be sure that the air shutter is the same distance from the burner orifice on both sides of the air shutter for proper burner fit up 10 Carefully replace the b...

Page 14: ...ing Routes and Components Important It is always best to locate the appliance in such a way that minimizes the number of offsets and horizontal vent length Sinceitisveryimportantthattheventingsystemma...

Page 15: ...e center line of the regulator I Clearance to service regulator vent outlet 6 feet 1 83 m minimum J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other ap...

Page 16: ...hes The vent pipe is now locked together Continue adding components per the pre planned vent system configuration Be certain that each succeeding vent component is securely fitted and locked into the...

Page 17: ...hole previously cut Secure with nails or screws Continue the vent run through the firestops See Figure 19 Figure 19 Vertical runs of this system which pass through ceilings require the use of ONE 1 ce...

Page 18: ...ews provided Before attachment of the termination run a bead of silicone sealant rated above 250 F on its outside edge too so as to make a seal to that exterior wall NOTE Wood screws can and should be...

Page 19: ...e as follows 1 Check areas of the venting system which are exposed to the elements for corrosion These will appear as rust spots or streaks and in extreme cases holes These components should immediate...

Page 20: ...materials including insulation to the vent system are maintained Vertical Through the Roof Applications Your Gas Fireplace has been approved for a Vertical installations up to 25 feet of vent run b Tw...

Page 21: ...toe resting on the groove in the left front log 12 Place right twig onto right side pin on rear log with toe resting all the way to the right on the right front log 13 Align and place top of glass fr...

Page 22: ...g Pilot Operation 1 FollowtheSAFETYandLIGHTINGINSTRUCTIONSforstanding pilot controls found in this manual and on labels found attached to the appliance CAUTION During the initial purging and subsequen...

Page 23: ...which must be lighted by hand When lighting the pilot follow these instructions exactly B Before lighting smell all around the appliance area for gas Be sure to smell next to the floor because some g...

Page 24: ...thermopile just below the tip A slight yellow flame may occur where the pilot flame and main burner flame meet The incorrect pilot flame is not touching the thermocouple or thermopile This will cause...

Page 25: ...pointment theservicepersonshouldcleandust lint and any light accumulation from the logs and the firebox area An extra soft brush should be used on the logs as they are extremely fragile a vacuum clean...

Page 26: ...ess the black and green wires female push ons attach to the gas valve An additional green wire and the red wire which are stripped and bare will attach to the 750 millivolt wall thermostat accessory o...

Page 27: ...26127 5 0111 Page 27 Wiring Diagram Figure 34 WIRING continued...

Page 28: ...ce glass frame assembly on a non abrasive surface The exterior of the glass frame assembly should be facing the non abrasive surface 7 Insert a putty knife between glass and bottom corners on frame Ca...

Page 29: ...h the pilot lit and the ON OFF switch in the OFF position Replace the faulty thermopile if the reading is below the specified minimum With the pilot in the ON position disconnect the thermopile leads...

Page 30: ...URNER ASSEMBLY 19 P 253 ORIFICE ANGLED FITTING 20 24429 ORIFICE HOLDER BRACKET 21 R 7572 JAMB NUT 22 P 244 ORIFICE 33 LPG 22 P 185 ORIFICE 52 NAT 23 26561 AIR SHUTTER BRACKET 24 23939 FIREBOX BOTTOM 2...

Page 31: ...26127 5 0111 Page 31 PARTS VIEW 1 9 4 2 3 4 6 4 8 10 11 12 14 15 16 28 29 31 36 37 38 39 40 41 42 43 44 45 30 17 18 19 20 21 22 24 25 26 27 32 34 35 23 13 33 5 7 29 47 9 46...

Page 32: ...IGHT 8 R 9694 CASTING DOOR LEFT 9 24191 FIREBOX SUPPORT BRACKET 2 REQUIRED 11 R 9549 CASTING LEG B 12 R 9548 CASTING LEG A PORCELAIN BLACK 1 R 9570 TOP INSERT RIGHT 2 R 9569 TOP INSERT LEFT 3 R 9568 C...

Page 33: ...26127 5 0111 Page 33 1 2 8 3 4 5 6 7 9 9 10 10 10 10 12 11 11 12 CASTING PARTS VIEW...

Page 34: ...to casting before fully tightening bolts as shown in Figure 37 9 Replace cast iron or stone inlay inserts into casting top Note Be sure to remove side shelf supports prior to removing cast iron top t...

Page 35: ...1 4 push on terminal from white wire on the fan control to the ON bottom tab on the switch 9 Insert AUTO OFF ON switch into rectangular notch on wire channel left 10 Install rheostat through hole in...

Page 36: ...y grounded three prong receptacle Do not cut or remove the grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wire for grounding can be purchased plugged...

Page 37: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 38: ...26127 5 0111 Page 38 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 39: ...ng the front of the direct vent fireplace the minimum clearances to combustible construction material are the following Top of appliance ceiling 36 inches Heater Corners 45 angle to Wall 4 inches Rear...

Page 40: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: