ICM/ICAD Motorized Valve
Installation, Programming, and Troubleshooting
Danfoss (USCO / MKS), 11 - 006
DKRCI.EI.HT0.A1. / 50H1639
11
Alarms
There are a number of alarms which are excellent indicators of improper installation or
set-up:
Description
ICM
alarm text Comments
No valve type selected
A1
At start-up
A1
and
CA
will be displayed
Controller fault
A2
Internal fault inside electronics
Input error
A3
Not applicable if
¡01
= or
¡02
=
When
¡03
= 1 and AI > mA
When
¡03
= and AI > mA or AI < mA
When
¡03
= 3 and AI >1 V
When
¡03
= 4 and AI >1 V or AI < 1 V
Low voltage of fail safe supply
A4
If 5 V d.c. < Fail safe supply
< 18 V d.c.
Check Supply to ICAD
A5
If supply voltage < 18 V d.c.
Problem
Possible cause and solution
The valve is not working and an A1 is
flashing in the display.
The ICM valve size was not selected in
parameter
¡26
. See the programming
section on page 9.
The valve does not appear to be opening
or closing properly
The ICAD was not mounted properly
on the valve stem.
Solution:
Check to
make sure that the ICAD was mounted
evenly on the ICM valve
The ICAD is not receiving a proper
input signal.
Solution:
Use the service
parameters (
¡51
for a mA input or
¡52
for a voltage input) to check the input
signal that the ICAD is receiving.
1.
.
The valve position feedback signal is not
working when using customer supplied
controller/PLC
A power supply was installed in the
4-0mA/0-0mA feedback loop.
The ICAD motor actuator supplies
the power for the 4-0mA/0-0mA
feedback loop.
Solution:
Remove any
power source that may be supplied to
the feedback loop.
Wiring problem.
Solution:
Check the
service parameter
¡53
to see what the
ICAD is outputting. If this does not
reveal anything, check the current
output (yellow and blue wires in ICAD
control cable) with an ammeter.
The feedback output signal was turned
off in parameter
¡06
.
Solution:
Check
to make sure the setting in parameter
¡06
is correct.
1.
.
3.
For all other problems, contact Danfoss.
Troubleshooting Tips
Summary of Contents for Vilter VSH
Page 2: ......
Page 30: ...2 4 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 54: ...3 24 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 74: ...4 20 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 144: ...5 70 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 156: ...7 4 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 158: ...8 2 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 204: ...8 48 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 206: ...A 2 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 210: ...B 4 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 216: ...C 6 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 219: ......
Page 221: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 242: ...E 12 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 248: ...G 2 Blank VSS VSM VSH VSSH Installation Operation and Maintenance Manual Emerson 35391SD ...
Page 249: ......