B - 5
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Warning Status Words
Statuses: Warning Status Word(s) – currently 20 warnings, so both Warning Status Word 1 and 2 are used, with each
position indicating an alarm:
MSB LSB
[Bit 15, Bit 14, Bit 13 ... Bit 3, Bit 2, Bit 1, Bit 0]
Table B-8. Warning Status Words
Word 1
Word 2
Bit 0 = Low Suction Pressure Warning
Bit 0 = Low Discharge 2 Pressure Warning
Bit 1 = Low Process Temperature Warning
Bit 1 = Low Discharge 2 Temperature Warning
Bit 2 = Low Process Pressure Warning
Bit 2 = Low Oil Filter In Pressure Warning
Bit 3 = Low Suction Temperature Warning
Bit 3 = Low Oil Filter Out Pressure Warning
Bit 4 = Low Crankcase Oil Temperature Start Warning
Bit 4 = Unused
Bit 5 = Low Oil Level Warning
Bit 5 = Unused
Bit 6 = High Discharge Pressure Warning
Bit 6 = Unused
Bit 7 = High Discharge 2 Pressure Warning
Bit 7 = Unused
Bit 8 = High Process Pressure Warning
Bit 8 = Unused
Bit 9 = High Discharge Temperature Warning
Bit 9 = Unused
Bit 10 = High Discharge 2 Temperature Warning
Bit 10 = Unused
Bit 11 = High Crankcase Oil Temperature Warning
Bit 11 = Unused
Bit 12 = High Filter Diff. Pressure Start Warning
Bit 12 = Unused
Bit 13 = High Level Shutdown Warning
Bit 13 = Unused
Bit 14 = Low Discharge Pressure Warning
Bit 14 = Unused
Bit 15 = Low Discharge Temperature Warning
Bit 15 = Unused