3 – 4
Section 3
•
Main Screen
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Control Parameter Box
The parameter boxes provide updated data on several
key control parameters.
Control Setpoint
The top box displays the desired control setpoint that is
set in the Compressor Control Screen.
Suction Press
Displays the current Suction Pressure value.
Suction Temp
Displays the current Suction Temperature value.
Discharge Press
Displays the current Discharge Pressure value.
Discharge Temp
Displays the current Discharge Temperature value.
Oil Press Diff
This is calculated as Oil Manifold Pressure minus Suction
Pressure
Oil Filter Diff
This is calculated depending on the Oil Monitoring set-
ting in the Configuration screen. When Oil Monitoring
Setting is set as:
a. No Oil Filter Monitoring
Oil Filter Differential is not calculated and value
displayed is NA.
b. Only Oil Filter In
Oil Filter Differential is calculated as Filter Inlet
Pressure minus Oil Manifold Pressure.
c. Oil Filter In and Oil Filter Out
Oil Filter Differential is calculated as Filter Inlet
Pressure minus Filter Outlet Pressure.
Oil Temp
Displays the current Oil Temperature value.
Motor Amperage
Displays the current motor current.
Press Ratio
Displays ratio of Absolute Discharge Pressure to Abso-
lute Suction Pressure.
Figure 3-4. Start Dialog Box