B - 13
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-16. Alarms/Trips Block (Page 2)
Ethernet IP
Address
Modbus
Address
Alarms/Trips (Page 1)
Data Type Value
Mode
Lower
Range
Higher
Range
N61:17
40417 High Process Pressure Trip
Setpoint #1
F-INT
(Currently
Unused)
Read-
Write
-15
350
N61:18
40418 Low Process Pressure Alarm
Setpoint #2
F-INT
(Currently
Unused)
Read-
Write
-15
300
N61:19
40419 Low Process Pressure Trip Set-
point #2
F-INT
(Currently
Unused)
Read-
Write
-15
300
N61:20
40420 High Process Pressure Alarm
Setpoint #2
F-INT
(Currently
Unused)
Read-
Write
-15
300
N61:21
40421 High Process Pressure Trip
Setpoint #2
F-INT
(Currently
Unused)
Read-
Write
-15
300
Table B-15. Alarms/Trips Block (Page 1) (continued)
Ethernet IP
Address
Modbus
Address
Alarms/Trips (Page 2)
Data Type Value
Mode
Lower
Range
Higher
Range
N62:0
40430
Low Suction Temperature Alarm
F-INT
Read-
Write
-100
210
N62:1
40431
Low Suction Temperature Trip
F-INT
Read-
Write
-100
210
N62:2
40432 High Discharge Temperature Alarm
F-INT
Read
NA
NA
N62:3
40433 High Discharge Temperature Trip
F-INT
Read
NA
NA
N62:4
40434 Low Crankcase Oil Temperature -
Start Alarm
F-INT
Read
NA
NA
N62:5
40435 Low Crankcase Oil Temperature -
Start Trip
F-INT
Read
NA
NA
N62:6
40436 Low Crankcase Oil Temperature -
Run Alarm
F-INT
Read
NA
NA
N62:7
40437 Low Crankcase Oil Temperature -
Run Trip
F-INT
Read
NA
NA
N62:8
40438 High Crankcase Oil Temperature
Alarm
F-INT
Read
NA
NA
N62:9
40439 High Crankcase Oil Temperature
Trip
F-INT
Read
NA
NA