Appendix A
•
Unloaders
A – 2
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table A-1. Type 1 Unloader - Cylinders: 2, 4, or 6
Unloading Percentage: 50% *
Unloader Tables
The following tables provide the status of Unloader Outputs for each type of unloading scheme at every step.
% Load
Compressor Start Output Unloader Output #1
% Unload
0 (OFF)
0
0
100
50
1
1
50
100
1
0
0
Table A-2. Type 2 Unloader - Cylinders: 4
Unloading Percentage: 25%, 50%, 75% | Single cylinder on Unloader Output #1 *
% Load
Compressor Start Output Unloader Output #1
(single cylinder)
Unloader Output #2
(double cylinder)
% Unload
0 (OFF)
0
0
0
100
25
1
1
1
75
50
1
0
1
50
75
1
1
0
25
100
1
0
0
0
Table A-3. Type 3 Unloader - Cylinders: 6 or 12
Unloading Percentage: 33%, 66% *
% Load
Compressor Start Output Unloader Output #1 Unloader Output #2
% Unload
0 (OFF)
0
0
0
100
33
1
1
1
66
66
1
0
1
33
100
1
0
0
0
* 0 = output OFF
1 = output ON
Table A-4. Type 4 Unloader - Cylinders: 8 or 16
Unloading Percentage: 25%, 50% *
% Load
Compressor Start Output Unloader Output #1 Unloader Output #2
% Unload
0 (OFF)
0
0
0
100
50
1
1
1
50
75
1
0
1
25
100
1
0
0
0