Section 6 • Alarms and Trips
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
Low Oil Filter In Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Filter Inlet Pressure
value from Measuring Instrument. There is no user configured setpoint.
Low Oil Filter In Pressure
Warning
Low Oil Filter In Pressure Inhibit
Low Oil Filter In Pressure
Trip
Filter Inlet Pressure <=
-66.5 Psig
Filter Inlet Pressure <= -66.5 Psig
Filter Inlet Pressure <=
-66.5 Psig
Low Oil Filter Out Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Filter Outlet Pressure
value from Measuring Instrument. There is no user configured setpoint.
Low Oil Filter Out
Pressure Warning
Low Oil Filter Out Pressure Inhibit
Low Oil Filter Out
Pressure Trip
Filter Outlet Pressure <=
-66.5 Psig
Filter Outlet Pressure <= -66.5 Psig
Filter Outlet Pressure <=
-66.5 Psig
Low Discharge #2 Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge 2 Pressure
value from Measuring Instrument. There is no user configured setpoint.
These safeties will be only active when No. of Cylinders set in Configuration screen is “12 cyl” or “16 cyl”.
Low Discharge 2 Pressure
Warning
Low Discharge 2 Pressure Inhibit
Low Discharge 2 Pressure
Trip
Discharge 2 Pressure <=
-66.5 Psig
Discharge 2 Pressure <= -66.5 Psig
Discharge 2 Pressure <=
-66.5 Psig
Low Discharge #2 Temperature:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge 2 Tempera-
ture value from Measuring Instrument. There is no user configured setpoint.
These safeties will be only active when No. of Cylinders set in Configuration screen is “12 cyl” or “16 cyl”.
Low Discharge 2
Temperature Warning
Low Discharge 2 Temperature
Inhibit
Low Discharge 2
Temperature Trip
Discharge 2 Temperature
<= -100 °F
Discharge 2 Temperature <= -100 °F
Discharge 2 Temperature
<= -100 °F