Section 6 • Alarms and Trips
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
Low Crankcase Oil Temperature - Start:
Below Messages will be displayed on Main screen when Oil Temperature value drops below configured set
-
points. Refer Figure 6- 2 for Alarm & Trip setpoints.
These safeties will be only active when Crankcase Oil Temp Changeover Timer is running.
Low Crankcase Oil Tem-
perature Start Warning
Low Crankcase Oil Temperature
Start Inhibit
Low Crankcase Oil
Temperature Alarm
Low Crankcase Oil Tem-
perature Trip
Oil Temperature <= Low
Crankcase Oil Tempera-
ture – Start Alarm Set-
point
Oil Temperature <= Low Crankcase
Oil Temperature – Start Alarm
Setpoint
Oil Temperature <=
Low Crankcase Oil
Temperature – Start
Alarm Setpoint
Oil Temperature <= Low
Crankcase Oil Tempera-
ture – Start Trip Setpoint
Low Crankcase Oil Temperature - Run:
Below Messages will be displayed on Main screen when Oil Temperature value drops below configured set
-
points. Refer Figure 6- 2 for Alarm & Trip setpoints.
These safeties will be only active once Crankcase Oil Temp Changeover Timer is lapsed.
Low Crankcase Oil
Temperature Alarm
Low Crankcase Oil Tem-
perature Trip
Oil Temperature <=
Low Crankcase Oil
Temperature – Run
Alarm Setpoint
Oil Temperature <= Low
Crankcase Oil Tempera-
ture – Run Trip Setpoint
High Crankcase Oil Temperature:
Below Messages will be displayed on Main screen when Oil Temperature value rises above configured setpoints.
Refer Figure 6- 2 for Alarm & Trip setpoints.
High Crankcase Oil Tem-
perature Warning
High Crankcase Oil Temperature
Inhibit
High Crankcase Oil
Temperature Alarm
High Crankcase Oil Tem-
perature Trip
Oil Temperature >= High
Crankcase Oil Tempera-
ture Alarm Setpoint
Oil Temperature >= High Crankcase
Oil Temperature Alarm Setpoint
Oil Temperature >=
High Crankcase Oil
Temperature Alarm
Setpoint
Oil Temperature >= High
Crankcase Oil Tempera-
ture Trip Setpoint