B - 7
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-9. Trip Status Words (Words 3 & 4)
Word 3
Word 4
Bit 0 = Low Suction Pressure Trip
Bit 0 = Compressor Interlock Trip
Bit 1 = Low Process Temperature Trip
Bit 1 = False Start
Bit 2 = Low Process Pressure Trip
Bit 2 = Starter Shutdown Trip
Bit 3 = Low Suction Temperature Trip
Bit 3 = Remote Comm Time out
Bit 4 = Low Crankcase Oil Temperature Trip
Bit 4 = IO Comm Trip
Bit 5 = Low Oil Pressure Diff. Trip
Bit 5 = Low Discharge Pressure Trip
Bit 6 = Low Oil Level Trip
Bit 6 = Low Discharge Temperature Trip
Bit 7 = High Discharge Pressure Trip
Bit 7 = Low Discharge 2 Pressure Trip
Bit 8 = High Discharge 2 Pressure Trip
Bit 8 = Low Discharge 2 Temperature Trip
Bit 9 = High Process Pressure Trip
Bit 9 = Low Oil Filter In Pressure Trip
Bit 10 = High Discharge Temperature Trip
Bit 10 = Low Oil Filter Out Pressure Trip
Bit 11 = High Discharge 2 Temperature Trip
Bit 11 = Unused
Bit 12 = High Crankcase Oil Temperature Trip
Bit 12 = Unused
Bit 13 = High Filter Differential Pressure Trip
Bit 13 = Unused
Bit 14 = High Level Shutdown Trip
Bit 14 = Unused
Bit 15 = High Motor Amps Trip
Bit 15 = Unused