Section 10
•
Input / Output States Screen
10 – 1
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Overview
This screen displays “Live Data” of all the Analog Inputs
/ Outputs and Digital Inputs / Outputs being monitored.
There are two pages of Inputs / Outputs (I/O) available
for viewing, see Figures 10-1 & 10-2.
This screen also takes a snapshot of all the I/O points
when the operator presses on “Freeze Data” button or if
the compressor experiences a trip condition. The Freeze
page displays the title that indicates whether the Freeze
data is saved due to trip condition or “Freeze Data” but-
ton was pressed by the operator, see Figures 10-3 & 10-
4. Latest Freeze data is shown in Freeze 1 tab. Up to five
Freeze pages can be saved. The oldest Freeze page will
be removed when more than five Freeze events occur.
These freeze events can be downloaded to a USB drive
through Data Backup screen.
NOTE
The format in which time is displayed on the Freeze page
does not change depending on time format selected
in the Configuration screen. Also values for Auxiliary
Analog Inputs like Discharge 2 Pressure & Discharge 2
Temperature will be only shown when Analog Input 1
Board is enabled from the Configuration screen, see
Figure 10-5.
Figure 10-1. Input/Output States Screen Page 1 - Live I/O Data