B - 1
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-1. Digital Inputs Block
MicroVission Communication Table
Scope
: MicroVission Programs – version 1.0 .
NOTES
:
• All ENUM variables are of INT (Integer) type
• All F-INT data types represent floating point values as INT types multiplied by 10
• All Pressures are in Psig
• All Temperatures are in Fahrenheit
• Modbus TCP addressing is PLC-style (Base 1) addressing
• On Error, Modbus TCP server only returns an error code of “Illegal Data Address”
• All registers returned (INT and F-INT) are 2 bytes long
• For Ethernet/IP, use INT data type and PLC-5 Word Range Read/Write MSG instructions
• Remote commands cannot be issued if the panel is in the “Remote Lock” mode
• Polling rates should not be less than 5 secs
• Writes to the MicroVission should only occur when a value needs to be changed
• Lower Range and Higher Range values mentioned are default values of MicroVission setpoints
• Users can modify Lower Range & Higher Range values from MicroVission Panel and accordingly maintain their
own table
Ethernet IP
Address
Modbus
Address
Digital Inputs
Data Type
Value
Mode
Lower
Range
Higher
Range
N50:0
40001 Setpoint 1/2
INT
0 = OFF, 1 = ON
Read
NA
NA
N50:1
40002 Remote Decrease
INT
0 = OFF, 1 = ON
Read
NA
NA
N50:2
40003 Remote Increase
INT
0 = OFF, 1 = ON
Read
NA
NA
N50:3
40004 Remote Start/Stop
INT
0 = OFF, 1 = ON
Read
NA
NA
N50:4
40005 Low Oil Level
INT
0 = OFF, 1 = ON
Read
NA
NA
N50:5
40006 High Level Shutdown
INT
0 = OFF, 1 = ON
Read
NA
NA
N50:6
40007 Compressor Auxiliary
INT
0 = OFF, 1 = ON
Read
NA
NA
Table B-2. Digital Outputs Block
Ethernet IP
Address
Modbus
Address
Digital Outputs
Data Type
Value
Mode
Lower
Range
Higher
Range
N51:0
40030 Oil Return Solenoid
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:1
40031 Unloader #4
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:2
40032 Unloader #3
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:3
40033 Unloader #2
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:4
40034 Unloader #1
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:5
40035 Trip
INT
0 = OFF, 1 = ON
(ON when no Trip)
Read
NA
NA
N51:6
40036 Oil Crank Case Heater
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:7
40037 Compressor Start
INT
0 = OFF, 1 = ON
Read
NA
NA
N51:8
40038 Remote Ready
INT
0 = OFF, 1 = ON
Read
NA
NA