Safety
Information
Introduction
Product
information
System
design
Mechanical
installation
Electrical
installation
Getting
started
Optimisation
Parameters
Technical
data
Component
sizing
Diagnostics
194
Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
Table 10-19 DC fuse and cable ratings (European)
Model
DC - current
A dc
DC voltage
V dc
DC fuses
DC Cable size
HRC
IEC class gG
UL class J
Semi-
conductor
IEC class aR
mm
2
AWG
SP1201
6.3
350
SP1202
8.3
SP1203
11.6
SP1204
13.3
SP2201
18.7
350
SP2202
26.6
SP2203
33.9
SP3201
50.8
350
SP3202
65.3
SP4201
82.3
350
SP4202
96.8
SP4203
125.8
SP5201
SP5202
SPMD1201
343
700
400
2 x 70
2 x 2/0
SPMD1202
400
560
2 x 95
2 x 4/0
SPMD1203
457
560
2 x 120
2 x 4/0
SPMD1204
552
560
2 x 120
2 x 4/0
SP1405
10.7
700
SP1406
134.
SP2401
18.7
700
SP2402
25.6
SP2403
35.4
SP2404
35.4
SP3401
42.8
700
SP3402
52.5
SP3403
68.3
SP4401
82.9
700
SP4402
101.3
SP4403
126.9
SP5401
168.4
700
SP5402
204.9
SP6401
250.1
700
SP6402
287.9
SPMA1401
250.1
700
SPMA1402
287.9
SPMD1401
343
700
400
2 x 70
2 x 2/0
SPMD1402
400
560
2 x 95
2 x 4/0
SPMD1403
457
560
2 x 120
2 x 4/0
SPMD1404
552
560
2 x 120
2 x 4/0
SP3501
6.5
835
SP3502
7.4
SP3503
10.2
SP3504
13.3
SP3505
19.4
SP3506
26.6
SP3507
32.7
SP4601
26.6
1005
SP4602
32.7
SP4603
43.6
SP4604
52.0
SP4605
62.9
SP4606
75.0
SP5601
101.6
1005
SP5602
119.8
SP6601
151.3
1005
250
2 x 95
2 x 4/0
SP6602
174.2
315
2 x 120
2 x 4/0
SPMA1601
151.3
1005
250
2 x 95
2 x 4/0
SPMA1602
174.2
315
2 x 120
2 x 4/0
SPMD1601
151.3
1005
250
2 x 95
2 x 4/0
SPMD1602
174.2
315
2 x 120
2 x 4/0
SPMD1603
203.3
350
2 x 120
2 x 4/0
SPMD1604
232.4
400
2 x 120
2 x 4/0
Summary of Contents for SP1201
Page 219: ......
Page 220: ...0471 0029 02 ...