Safety
Information
Introduction
Product
information
System
design
Mechanical
installation
Electrical
installation
Getting
started
Optimisation
Parameters
Technical
data
Component
sizing
Diagnostics
Unidrive SP Regen Installation Guide
27
Issue Number: 2 www.controltechniques.com
Table 3-19 690V (690V
±
10%) SFF Inductor
The inductors are standard three phase inductors (rated at Unidrive SP
Regen drive rated current). They carry only 50/60Hz current with a
negligible amount of high frequency current. The above switching
frequency filter inductors are calculated at 4% of the regen drives rating
using the following formula. A tolerance can be applied to the calculated
value in the range of, -10% to +30%.
L switching frequency filter mH = VLL /
√
3 x 1 / Irated x 0.04 x 1 / (2 x pi
x f).
Where:
VLL =
Supply voltage line-to-line
f = Supply frequency
Irated = Drive rated current
This calculation also gives the correct inductance value for a 480V, 60Hz
supply.
Table 3-20 200V (200V to 240V
±
10%) SFF Capacitors
Table 3-21 400V (380V to 480V
±
10%) SFF Capacitors
Table 3-22 575V (500V to 575V
±
10%) SFF Capacitors
Drive
Part number
mH
Arms
Heavy Duty
Normal Duty
SP4601
SP4601
4401-1211
1.40
22.0
SP4602
4401-1211
1.40
22.0
SP4603
SP4602
4401-1213
1.40
36.0
SP4604
SP4603
4401-1213
1.40
36.0
SP4605
SP4604
4401-1214
1.20
43.0
SP4606
SP4605
4401-1215
1.00
52.0
SP5601
SP4606
4401-1216
0.80
63.0
SP5602
SP5601
4401-1217
0.60
85.0
SP6601
SP5602
4401-1218
0.50
100.0
SP6602
SP6601
4401-1219
0.40
125.0
SPMA1601
4401-1218
0.50
100.0
SPMD1601
4401-1218
0.50
100.0
SPMA1602
SPMA1601
4401-1219
0.40
125.0
SPMD1602
SPMD1601
4401-1219
0.40
125.0
SPMA1602
4401-1220
0.35
144.0
SPMD1602
4401-1220
0.35
144.0
SPMD1603
SP6602
4401-1220
0.35
144.0
SPMD1604
SPMD1603
4401-1221
0.30
168.0
SPMD1604
4401-1222
0.26
192.0
Drive
Part number
uF
Arms
Heavy Duty
Normal Duty
SP1203
SP1203
1664-1074
7
1.7
SP1204
SP1204
SP2201
SP2201
SP2202
SP2202
1664-2174
16.6
4.3
SP2203
SP2203
SP3201
SP3201
SP3202
SP4201
SP3202
1665-8324
32
11
SP4202
SP4201
SP4203
SP4202
SP5201
SP4203
1664-2644
64
17
SP5202
SP5201
SPMD1201
SP5202
SPMD1202
SPMD1201
2 x 1664-2644
2 x 64
2 x 17
SPMD1203
SPMD1202
SPMD1204
SPMD1203
SPMD1204
NOTE
Drive
Part number
uF
Arms
Heavy Duty
Normal Duty
SP1405
SP1405
1610-7804
8
4.3
SP1406
SP1406
SP2401
SP2401
SP2402
SP2402
SP2403
SP2404
SP2403
1665-8324
32
11
SP3401
SP2404
SP3402
SP3401
SP3403
SP3402
SP4401
SP3403
SP4401
SP4402
SP4402
1665-8484
48
17
SP4403
SP4403
SP5401
SP5401
SP5402
SP5402
SP6401
SP6401
SP6402
SPMA1401
SPMA1401
SPMA1402
SPMD1401
SPMD1401
SPMD1402
SP6402
1665-8774
77
26
SPMA1402
SPMA1402
SPMD1402
SPMD1403
SPMD1403
SPMD1404
SPMD1404
2 x 1665-8394
2 x 39
2 x 13
Drive
Part number
uF
Arms
Heavy Duty
Normal Duty
SP3505
SP3505
1666-8113
11.2
5
SP3506
SP3506
SP3507
SP3507
SP4601
SP4601
SP4602
SP4602
SP4603
SP4603
SP4604
SP4604
SP4605
SP4605
SP4606
SP4606
SP5601
SP5601
SP5602
SP6601
SP5602
1666-8223
22.5
10
SP6602
SP6601
SPMA1601
SP6602
SPMA1602
SPMA1601
SPMD1601
SPMA1602
SPMD1602
SPMD1601
SPMD1603
SPMD1602
SPMD1604
SPMD1603
2 x 1666-8233
2 x
22.5
2 x 10
SPMD1604