Safety
Information
Introduction
Product
information
System
design
Mechanical
installation
Electrical
installation
Getting
started
Optimisation
Parameters
Technical
data
Component
sizing
Diagnostics
126
Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
Parameter value
Parameter string
Mode
Comments
0
0-20
0 - 20mA
1
20-0
20 - 0mA
2
4-20.tr
4 -20mA with trip on loss
Trip if I < 3mA
3
20-4.tr
20 - 4mA with trip on loss
Trip if I < 3mA
4
4-20
4 - 20mA with no trip on loss
5
20-4
20 - 4mA with no trip on loss
0.0% if I < 4mA
6
VOLt
Voltage mode
7
th.SC
Thermistor with short circuit detection
TH trip if R > 3k3
TH reset if R < 1k8
THS trip if R < 50R
8
th
Thermistor without short circuit detection
TH trip if R > 3k3
TH reset if R < 1k8
9
th.diSp
Thermistor display only with no trip
7.16
T8 analogue input 3 scaling
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
3
1
1
1
Range
Regen
0.000 to 4.000
Default
Regen
1.000
Update rate
Background
7.17
T8 analogue input 3 invert
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
Default
Regen
0
Update rate
Background
7.18
T8 analogue input 3 destination
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
1
2
1
1
1
1
Range
Regen
Pr
0.00
to Pr
21.51
Default
Regen
Pr
0.00
Update rate
Background
7.19
T9 analogue output 1 source
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
2
1
1
1
1
Range
Regen
Pr
0.00
to Pr
21.51
Default
Regen
Pr
4.01
Update rate
Background
Summary of Contents for SP1201
Page 219: ......