If Pr
10.34
is set to zero then no auto reset attempts are made. Any other value will cause the drive to automatically reset following a trip for the
number of times programmed. Pr
10.35
defines the time between the trip and the auto reset (this time is always at least 10s for OI.AC, OI.br trips,
etc.). The reset count is only incremented when the trip is the same as the previous trip, otherwise it is reset to 0. When the reset count reaches the
programmed value, any further trip of the same value will not cause an auto-reset. If there has been no trip for 5 minutes then the reset count is
cleared. Auto reset will not occur on a UU, Et, EEF or HFxx trips. When a manual reset occurs the auto reset counter is reset to zero.
If this parameter is 0 then Pr
10.01
(Drive healthy) is cleared every time the drive trips regardless of any auto-reset that may occur. When this
parameter is set the 'Drive healthy' indication is not cleared on a trip if an auto-reset is going to occur.
If stop on low priority trips is selected the drive will stop before tripping except in regen mode where the drive trips immediately. Low priority trips are:
th, ths, Old1, cL2, cL3, SCL.
10.34
No. of auto-reset attempts
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Range
Regen
0 to 5
Default
Regen
0
Update rate
Background
10.35
Auto-reset delay
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
1
Range
Regen
0.0 to 25.0 s
Default
Regen
1.0
Update rate
Background
10.36
Hold drive healthy until last attempt
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Default
Regen
0
Update rate
Background
10.37
Action on trip detection
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
Range
Regen
0 to 3
Default
Regen
0
Update rate
Background
Braking IGBT trip mode
Stop on low priority trips
0
Trip
No
1
Trip
Yes
2
Disable
No
3
Disable
Yes