Safety
Information
Introduction
Product
information
System
design
Mechanical
installation
Electrical
installation
Getting
started
Optimisation
Parameters
Technical
data
Component
sizing
Diagnostics
196
Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
10.4 Component data
The following parts may be used:
•
Motoring drive
•
Regen drive
•
Regen inductor
•
Softstart resistor
•
Switching frequency filter (optional)
•
EMC filter (optional)
•
Varistors
•
Fusing
•
Contactors
•
Overloads
In addition to the above the additional items are also required to
assemble a Unidrive SP Regen
Brake Resistor replacement
system:
•
Isolating transformer
•
DC bus diode
10.4.1 Regen inductors
The regen inductor duty is very arduous, and therefore, correct
component selection is critical. The most sensitive aspect being the
inductor linearity. Only inductors specified in this installation guide
should be used.
The regen inductor supports the difference between the PWM voltage
from the Regen drive and the sinusoidal voltage from the supply. One
three-phase regen inductor is required per Regen drive.
Each regen inductor is fitted with a 170°C thermistor mounted in the
centre coil. The thermistor is set to 170°C at which point the resistance is
1000
Ω
, beyond 170°C a rapid rise in resistance will be seen.
If the permissible cable lengths are exceeded additional cooling may be
required for the regen inductors, refer to section 4.4.4
Table 10-21 200V Regen inductor specifications
Table 10-22 400V Regen inductor specifications
The internal EMC filter must be removed from drive.
CAUTION
The regen inductors have a normal operating temperature of
approximately 170°C depending upon the ambient and the
motor cable lengths. Care must be taken so that this does not
create a fire risk.
NOTE
CAUTION
NOTE
Inductor part
number
Amps
mH
Losses
W
L
mm
D
mm
H
mm
Weight
kg
Fixing centres (x * y)
mm
Fixing
mm
Fixing
type
4401-0310
9.6
3.5
71
215
180
200
10
120 x 140
9
A
4401-0311
11.0
2.7
72
215
180
200
11
120 x 140
9
4401-0312
15.5
2.2
116
215
180
200
12
120 x 140
9
4401-0313
22
1.6
157
215
180
200
15
120 x 140
9
4401-0314
31
1.10
193
270
180
240
17
160 x 140
9
4401-0315
42
0.81
200
270
200
240
24
160 x 160
9
4401-0316
56
0.6
264
325
220
320
32
200 x 180
11
4401-0317
68
0.5
299
325
220
320
33
200 x 180
11
4401-0318
80
0.4
298
325
220
320
39
200 x 180
11
4401-0319
105
0.32
338
370
260
360
55
240 x 220
11
4401-0320
130
0.26
394
375
280
360
65
240 x 240
11
4401-0321
156
0.22
475
395
280
360
77
240 x 240
11
4401-0322
192
0.18
526
395
280
360
97
240 x 240
11
4401-0323
250
0.14
610
430
300
410
110
280 x 260
11
4401-0324
312
0.11
776
430
300
410
120
280 x 260
11
4401-0325
350
0.10
863
490
320
480
130
320 x 260
11
Inductor part
number
Amps
mH
Losses
W
L
mm
D
mm
H
mm
Weight
kg
Fixing centres (x * y)
mm
Fixing
mm
Fixing
type
4401-0001
9.5
6.32
125.0
200
180
215
12
120 x 140
9
A
4401-0002
12
5.00
146.0
200
180
215
14
120 x 140
9
4401-0003
16
3.75
175.0
240
180
270
17
160 x 140
9
4401-0004
25
2.40
210.0
240
180
270
24
160 x 160
9
4401-0005
34
1.76
285.0
320
220
325
32
200 x 180
11
4401-0006
40
1.50
310.0
320
220
325
33
200 x 180
11
4401-0007
46
1.30
320.0
320
220
325
39
200 x 180
11
4401-0008
60
1.00
345.0
360
260
370
55
240 x 220
11
4401-0009
70
0.78
415.0
360
260
370
65
240 x 240
11
4401-0010
96
0.63
515.0
360
260
370
75
240 x 240
11
4401-0011
124
0.48
585.0
360
260
370
95
240 x 240
11
4401-0012
156
0.38
645.0
410
300
430
110
280 x 260
11
4401-0013
180
0.33
775.0
410
300
430
120
280 x 260
11
4401-0014
200
0.30
845.0
480
320
490
130
320 x 260
11
4401-0015
300
0.20
1760.0
480
320
490
140
320 x 240
11
4401-0205-00
350
0.16
1500
500
320
570
165
320 x 260
11
Summary of Contents for SP1201