Example
Figure D-3: Redundancy Setup Connections
A. Gateway A
B. Gateway B
C. PC/Laptop
D. Primary Ethernet
E. Secondary Ethernet
Once the Gateways have finished the pairing process, Gateway A will appear as the current
active Gateway on the left hand side and Gateway B will be the standby Gateway on the
right (note that left/right hand appearance can be changed on the Redundancy System
Settings page). If significant configuration changes need to be downloaded to the standby
Gateway, it may temporarily go offline shortly after the pair process is complete. This is
expected behavior and does not represent instability in the system.
D.4
Mounting and connections
Redundant Gateways follow similar mounting and connection practices as a standalone
Gateway. Refer to
for more information. In addition to the standard practices,
the following considerations should be taken when installing redundant Gateways.
D.4.1
Mounting
The redundant Gateways should be mounted in a location that allows convenient access
to the process control network as well and provides good coverage for the wireless field
network.
The redundant Gateway antennas should be mounted at the same height and be spaced
between 3–9 ft. (1–3 m) horizontally. This is to ensure that they provide identical coverage
for the wireless field network and to help eliminate coverage gap in the event of a switch
over.
D.4.2
Ethernet
An Ethernet connection to the host system will support Modbus TCP, OPC, AMS
™
Wireless
Configurator, and HART-IP
™
protocols. When using this architecture, connect the
secondary Ethernet port on Gateway A directly to the secondary Ethernet port on Gateway
B. Then connect the primary Ethernet ports for both Gateways to a process control
Redundancy
Reference Manual
September 2020
00809-0200-4420
88
Emerson.com/Rosemount
Summary of Contents for Smart Wireless Gateway 1420
Page 1: ...Reference Manual 00809 0200 4420 Rev HE September 2020 Emerson Wireless 1420 Gateway ...
Page 34: ...Installation Reference Manual September 2020 00809 0200 4420 34 Emerson com Rosemount ...
Page 42: ...Commissioning Reference Manual September 2020 00809 0200 4420 42 Emerson com Rosemount ...
Page 62: ...Troubleshooting Reference Manual September 2020 00809 0200 4420 62 Emerson com Rosemount ...
Page 84: ...DeltaV Ready Reference Manual September 2020 00809 0200 4420 84 Emerson com Rosemount ...
Page 95: ...Reference Manual 00809 0200 4420 September 2020 Emerson com Rosemount 95 ...