33
Reference Manual
00809-0100-4024, Rev CA
Mechanical Installation
March 2020
Mechanical Installation
2.7
Mounting the process seal antenna
Figure 2-22. Process Seal Antenna Dimensions
Dimensions are in inches (millimeters).
2.7.1
Preparations
It is important that the tank flange surface is flat. The maximum deviation must be within the following
specifications as illustrated:
7.87 (200)
21.65 (550) 4 in. process seal
25.59 (650) 6 in. process seal
6.30 (160) 4 in. process seal
8.58 (218) 6 in. process seal
d
Flange surface tolerance:
d<
±
0.05 mm