Refrigerant Charge Requirements
Total R-407C refrigerant charge will be required only if units are evacuated during installation or
maintenance. For safe and effective operation, refer to pressures in
5.4.2 - Piping Connections and
Total Refrigerant = Units and Lines
Table 7
Line charges—refrigerant per 100 ft. (30m) of Type L copper tube
Line Size,
O.D., in.
R-407C, lb/100 ft. (kg/30m)
Liquid Line
Suction Line
3/8
3.7 (1.7)
—
1/2
6.9 (3.1)
—
5/8
11.0 (5.0
0.4 (0.2)
3/4
15.7 (7.1)
0.6 (0.3)
7/8
23.0 (10.4)
1.0 (0.4)
1-1/8
—
1.7 (0.7)
1-3/8
—
2.7 (1.1)
Table 8
Equivalent lengths for various pipe fittings, ft (m)
Copper Pipe
OD, in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow
Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2
0.8 (0.24)
1.3 (0.39)
0.4 (0.12)
2.5 (0.76)
0.26 (0.07)
7.0 (2.13)
4.0 (1.21)
5/8
0.9 (0.27)
1.4 (0.42)
0.5 (0.15)
2.5 (0.76)
0.28 (0.08)
9.5 (2.89)
5.0 (1.52)
3/4
1.0 (0.3)
1.5 (0.45)
0.6 (0.18)
2.5 (0.76)
0.3 (0.09)
12.0 (3.65)
6.5 (1.98)
7/8
1.45 (0.44)
1.8 (0.54)
0.8 (0.24)
3.6 (1.09)
0.36 (0.1)
17.2 (5.24)
9.5 (2.89)
1-1/8
1.85 (0.56)
2.2 (0.67)
1.0 (0.3)
4.6 (1.4)
0.48 (0.14)
22.5 (6.85)
12.0 (3.65)
1-3/8
2.4 (0.73)
2.9 (0.88)
1.3 (0.39)
6.4 (1.95)
0.65 (0.19)
32.0 (9.75)
16.0 (4.87)
1-5/8
2.9 (0.88)
3.5 (1.06)
1.6 (0.48)
7.2 (2.19)
0.72 (0.21)
36.0 (10.97)
19.5 (5.94)
Refrigerant trap = Four times equivalent length of pipe per this table
Table 9
Connection sizes and torque
Size OD Cu
Model Tons
Coupling Size
Torque Ib-ft.
3/8
1 and 1.5
#6
10-12
5/8
1 and 1.5
#11
35-45
NOTE
If field-supplied refrigerant piping is installed, R-407C refrigerant must be added to the
system.
Table 10
Refrigerant charge
Unit Type
Model #
Charge R-407C *
oz (kg)
60Hz
Self Contained-Air
MM*12A/F
42 (1.19)
Self Contained-Water
MM*14W/G
27 (0.77)
Split Evaporator-Air
MM*12E/K
3 (0.085)
Self Contained-Air
MM*18A/F
49 (1.39)
Self Contained-Water
MM*20W/G
28 (0.79)
Split Evaporator-Air
MM*18E/K
4 (0.11)
Split Condensing Unit
PFH014A-_L7
134 (3.80)
Split Condensing Unit
PFH020A-_L7
134 (3.80)
Self-contained DX units, split-system evaporators and split-system condensing units are pre-charged with R-407C refrigerant.
Use
to determine the charge contained in Liebert pre-charged R-407C line sets. Use
to determine the
charge to be added for field-fabricated refrigerant lines.
* For units with Hot Gas Reheat coil, add 18oz (0.51kg) refrigerant to listed values.
Summary of Contents for PFH020A-L
Page 3: ......
Page 74: ...Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer User Guide ...
Page 77: ...5 Troubleshooting 37 Vertiv Liebert PFH Installer User Guide ii ...
Page 86: ...Figure 2 6 General piping arrangement Vertiv Liebert PFH Installer User Guide 9 ...
Page 105: ...Vertiv Liebert PFH Installer User Guide 28 This page intentionally left blank ...
Page 109: ...Vertiv Liebert PFH Installer User Guide 32 This page intentionally left blank ...
Page 116: ......