Problem
Cause
Remedy
Compressor cycles on locked
rotor
Low line voltage
Check line voltage and determine location of voltage drop.
Compressor motor defective
Check for motor winding short or ground.
Single phasing
Check voltage across all 3 legs at contactor. Correct source of problem.
Motor burnout
Check control panel for welded
contactor contacts or welded overload
contacts.
Replace defective components.
Table 5.1 Troubleshooting (continued)
Vertiv
| Liebert PFH Installer/User Guide |
38